Laserfiche WebLink
NDE <br /> INDIVIDU—*ANK/LINE/LEAK DETECTOR TEREPORT <br /> NDE ENVIRONMENTAL CORPORATION <br /> TEST DATE: April 12, 1995 WORK ORDER NUMBER: 963990 <br /> CLIENT: ULTRAMAR INC SITE: ULTRAMAA 492 <br /> TANK INFORMATION <br /> Tank ID: 1 Bottom to top fill in inches: 122.0 <br /> Product: REG UNLEAD Bottom to grade fill in inches: 132.0 <br /> Capacity in gallons: 10,000 Fill pipe length in inches: 28.0 <br /> Diameter in inches: 94.00 Fill pipe diameter in inches: 4.0 <br /> Length in inches: 337 Stage I vapor recovery: coAx <br /> Material: STEEL Stage II vapor recovery: ASSIST <br /> Tank: No <br /> Manifolded Vent: YES <br /> V/R: No <br /> - COMMENTS <br /> TANK TEST RESULTS LEAK DETECTOR RESULTS <br /> Test method: Alert 1000 New/passed Failed/replaced <br /> Psi at tank bottom: 2.01 detector detector <br /> Fluid level in inches: 75.00 Test method: FTA <br /> UFT/OFT: UFT Make: RED JACKET <br /> Fluid volume in gallons: 8,577 Model: D.L.D. <br /> Water level in inches: 0.00 S/N: 109906086 <br /> Test time: 00:11-02:26 Open time in sec: <br /> Number of thermisters: Holding psi: 13 <br /> Specific gravity: 0.745 Resiliency cc: 90 <br /> Water table depth in inches: 240.00 Test leak rate ml/min: <br /> Determined by(method): OBSERVATIo Metering psi: <br /> Leak rate in gph: -0.005 Calib. leak in gph: 3.00 <br /> RESULT: PASS RESULT: FAIL <br /> COMMENTS ,_COMMENTS <br /> failed at 3 end 9 <br /> LINE TEST RESULTS <br /> ULLAGE TESTRESULTS <br /> Test method: Alert 1050 Material: FIBERGLASS <br /> Test time: 02:43-02:55 Diameter(in): 2.0 <br /> Ullage volume: 1,423 Length (ft): 40.0 <br /> Ullage pressure: 1.50 Test psi: 50 <br /> RESULT: PASS Bleedback cc: 75 <br /> DATA FOR UTS-4T ONLY: Test time (min): 30 <br /> Test 1:start time: 00:26 <br /> Time of test 1: finish psi: 50 <br /> Temperature: vol change cc: 5 <br /> Test 2:start time: 00:36 <br /> Flow rate(cfh): finish psi: so <br /> Time of test 2: vol change cc: 0 <br /> Temperature: Test 3:start time: 00:46 <br /> finish psi: 50 <br /> Flow rate(cfh): <br /> vol change cc: 0 <br /> Time of test 3: Final gph: 0.003 <br /> Temperature: RESULT: PASS <br /> Flow rate(cfh): Test type:ACURite <br /> COMMENTS Pump type: PRESSURE Pump make: RED JACKET <br /> COMMENTS <br /> 8906 WALL STREET SUITE 306,AUSTIN TEXAS 78754 512 719-4633 <br />