INDIVIDUWANK/LINE/LEAK DETECTOR To REPORT NDE <br /> NDE ENVIRONMENTAL CORPORATION <br /> TEST DATE: April 12, 1995 WORK ORDER NUMBER: 963990 <br /> CLIENT: ULTRANAR INC SITE: ULTRANAR 492 <br /> TANK INFORMATION <br /> Tank ID: 3 Bottom to top fill in inches: 120.0 <br /> Product: PLUS Bottom to grade fill in inches: 127.0 <br /> Capacity in gallons: 10,000 Fill pipe length in inches: 27.0 <br /> Diameter in inches: 93.00 Fill pipe diameter in inches: 4.0 <br /> Length in inches: 344 Stage I vapor recovery: COAX <br /> Material: STEEL Stage II vapor recovery: ASSIST <br /> Tank: No <br /> Manifolded Vent: YES <br /> V/R: No <br /> '..AOMMENTS <br /> TANK TEST RESULTS LEAK DETECTOR RESULTS <br /> Test method: Alert 1000 New/passed Failed/replaced <br /> Psi at tank bottom: 2.13 detector detector <br /> Fluid level in inches: 79.00 Test method: FTA <br /> UFT/OFT UFT Make: RED JACKET <br /> Fluid volume in gallons: 9,063 Model: D.L.D- <br /> Water level in inches: 0.00 S/N: 111951534 <br /> Test time: 00:11-02:40 Open time in sec: <br /> Number of thermisters: Holding psi: 20 <br /> Specific gravity: 0.748 Resiliency cc: 100 <br /> Water table depth in inches: 240.00 Test leak rate ml/min: <br /> Determined by(method): OBSERVATIO Metering psi: <br /> Leak rate in gph: 0.018 Calib. leak in gph: 3.00 <br /> RESULT: PASS RESULT: FAIL <br /> COMMENTS COMMENTS <br /> faed at 3 and 9 gph <br /> LINE TEST RESULTS <br /> ULLAGE TEST RESULTS LINE A <br /> Test method: Alert 1050 Material: FIBERGLASS <br /> Test time: 03:05-03:15 Diameter(in): 2.0 <br /> Ullage volume: 937 Length(ft): 40.0 <br /> Ullage pressure: 1.50 Test psi: 50 <br /> RESULT: PASS Bleedback cc: e0 <br /> DATA FOR UTS-4T ONLY: Test time(min): 30 <br /> Test 1:start time: 00:59 <br /> Time of test 1: finish psi: so <br /> Temperature: vol change cc: 6 <br /> Flow rate (cfh): Test 2:stan 09 <br /> ;an time:psi: 01:so <br /> Time of test 2: vol change cc: o <br /> Temperature: Test 3:stars time: 01:19 <br /> Flow rate(cfh): finish psi: 50 <br /> Time of test 3: vol change cc: e <br /> Final gph: 0.003 <br /> Temperature: RESULT: PASS <br /> Flow rate (cfh): Test type: ACURite <br /> -'`COMMENTS Pump type: PRESSURE Pump make: RED JACKET <br /> COMMENTS <br /> 8906 WALL STREET SUITE 306,AUSTIN TEXAS 78754 512 719-4633 <br />