Triangle Environmental, Inc. <br /> USTMONITOR CERTIFICATIONSUMMARYSHEET <br /> Client: <br /> Conoco Phillips Co. <br /> 600 N Dairy Ashford Facility # 2705445 <br /> Houston, TX 77079 <br /> est Date: 8/ 6/04 <br /> Facility: 2705445 <br /> Facility # 2705445 Work#: 20006918 <br /> County: SAN JOAQUIN <br /> 1206 E MARCH LN <br /> Cross Street: <br /> STOCKTON, CA 95210 <br /> Monitor model: VEEDER-ROOT TLS-350 <br /> Serial#: 10813987205005 Certification Result: PASS <br /> Sensor Type: Quantity: Result: <br /> Tank Annular : 3 PASS/ Annular Type: DRY <br /> Waste Oil Annular : 0 N/A AuctibleAlarm? Yes <br /> Waste Oil Sump: 0 N/A Visual Alarm? Yes <br /> Vadose Wells : 0 N/A Fail Safe? Yes <br /> Line Pressure : 0 N/A Positive Shut-oft? Yes <br /> Turbine Sump : 3 PASS Gauge Only Result: Pass <br /> Line Trench : 0 N/A ATG Monthly? No <br /> Fill Sump : 0 N/A ATG CSLD? No <br /> Comments: Inspector requested to take boot off the secondary containment of the product line in the 91 <br /> turbine sump. <br /> This certifies that the monitor and sensors,as listed above,are operational and calibrated per the <br /> manufacturer's specification. / <br /> Inspected By: <br /> Ronnie Humphries \vim'•'�- <br />