Laserfiche WebLink
7.UNDER-DISPENSER CONTAINMENT C TESTING <br /> Test Method Developed By: ❑UDC Manufacturer ® Industry Standard ❑ Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used:I N C 0 N SUMP TESTER Equipment Resolution: 0.002" <br /> �. <br /> UD -47-8 UDC#9-10 UDC# UDC# <br /> UDC Manufacturer: Bendel Bendel <br /> UDC Material: Fiberglass Fiberglass — <br /> UDC Depth: 34" 34" <br /> Height from UDC Bottom to Top 12" 12" <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 14" 14" <br /> Lowest Electrical Penetration_ <br /> Condition of UDC prior to Dry Dry <br /> testing: <br /> Portion of UDC Tested' 27 Penetrations 2"/Penetrations <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both ❑Yes ❑No ®NA Elves ❑No ®NA ❑Ycs ❑No ❑NA ❑Yrs []No ❑NA <br /> product and water)?* - — <br /> Turbine shutdown res once time N/A NIA <br /> Is system programmed for fail- ®NNo Elves ❑No ❑NA Elves ❑No ❑mt❑Yes ❑ <br /> safe shutdown?` <br /> Was fail-safe verified to be Elves ❑No ®NA Elves ❑No ®NA Elves ❑No [INA Elves ❑No ❑NA <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and 10 min 1D min <br /> starting test — <br /> Test Start Time: 11:10am 11:46am <br /> Initial Reading(P4): 5.7515" 6.9073" --- <br /> Test End Time: 11:25am 12:01pm <br /> Final ReadingRF): 5.7515" 6.9067" <br /> Test Duration: 15min 15min <br /> pPass/Fail <br /> Reading(RF-R,): 0.000" -0.0006" <br /> reshold or Criteria: +I-0.002" +1-0.002" _ . +/-0.002"t. ®Pass ❑FailPass ❑Fail ❑Pass ❑Fail ❑Pass ❑Failremoved fortestin ? ®Yes ❑No ❑NA ®Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA properly replaced and ®Yes ❑No ❑NA ®Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> ctional after testing? <br /> Comments (include information on repairs made prior to testing and recommended follow-up for failed tests) <br /> ABOVE IS THE LAST OF TWO BACK TO BACK 15 MINUTE TESTS ; <br /> ' If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />