Laserfiche WebLink
1 t <br /> �l <br /> I'>,AY 0 3 ZUI, <br /> LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test ENVIRONMENTAL HEALTH <br /> Work Order: 2331996 Date: 5/3/2017 <br /> Site Name/ID: DP&DK INV. INC./DP&DK <br /> Address: 1206 E. MARCH LANE MARCH LANE SHELL <br /> City: STOCKTON State: CA Zip: 95210 <br /> Tank ID 1 2 3 <br /> Product REGULAR PREMIUM Diesel <br /> Product Line 1 1 1 <br /> Tested From 9 9 9 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-200C Vaporless LD-200C Vaporless LD-200 <br /> Serial No. 07061368 01110513 12121061 <br /> Pump Operating Pressure(psi) 29.00 30.00 33.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 32.00 30.00 33.00 <br /> N/A for Electronic LD's <br /> Resiliency(ml) 150.00 200.00 145.00 <br /> NIA for Electronic Lo's <br /> Metering PSI 15 12 20 <br /> *N/A for Electronic LD's <br /> Opening Time(sec) 30 3 5 <br /> N/A for Electronic LD's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Jesus Saldivar Certification#: 115237 <br /> Technician Signature: <br /> J'4. : Expire Date: 12/27/2018 <br /> Environmental Compliance for Petroleum Systems <br /> ©2017 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />