A B C p E <br /> F <br /> 5UOYANC:Y C:ALC:ULATIONS, FOR 15, OOO COAL. DOU5LE WALL TANK <br /> SAMPLE BUOYANCY AT1 FQR 1 CALCULATIONS / DEADMEN ANCHORS <br /> FINISH 30. 08' 12. 08' <br /> SURFACE b 1 <br /> 0 2 MANWAY (TYP) <br /> 21 do <br /> ' <br /> " CONCRETE SLAB BACKFiLL COLUMN e e T- <br /> 4. <br /> ` (TYP 5ot!4 SIDES) <br /> 4. 50' .5. 00' BURY <br /> I CONCRETE DEADMEN <br /> 1' x I' x 28' LONG fo' THICK REINF. <br /> H ■ 5. 54' CONC. SLAB. PEA GRAVEL <br /> 5. 04' <br /> _ _ _ UjG. FUEL TANK <br /> 10. 08' (TYP) <br /> INSTALL PRE-ENGINEERED <br /> SHORING SYSTEM ON ALL <br /> SIDES <br /> DE5CRIPTION <br /> I. BACKFILL COLUMNS " <br /> 1' x 14. 58' HIGH x 28' LONG 408 C. F. INSTALL <br /> _ L = 26. 08' EU) DEADMEN <br /> EVEN WITH OUTSIDE EDGE <br /> CALCULATION OF TANKS <br /> NASI$ W = 406 C. F. x 2 x 60 LBS / C. F. <br /> 1. WATER CABLE AT 50TT01`i OF CONCRETE SLAB <br /> (}) W 48, 989 LBS. _ (L �12' PEA GRAVEL (L <br /> 2. SUBMEWSED WEIGHTS : 2. CONCRETE DEADMEN BED ' =' <br /> MATERIAL I' x 1' HIGH x 28' LONCs ■ 28 G. F. FILTER FABRIC LINE <br /> PEA GRAVEL 60. 0 POUNDS PER CUBIC FOOT CALCULATIONS <br /> REINFORCED CONCRETE 81. b POUND$ PER CUBIC FOOT 121 DEADMEN ANGHO 24' 3 - +Yo CONT. <br /> 2 WATER 1. 48 GALLONS PER CUBIC FOOT FULL LENGTH OF <br /> W ■ 28 C_ F. x 2 x 60 L55 / G. F. 2 - . G . TANK + 2'-0' BETWEEN ANY 2 <br /> WATER 62. 4 POUNDS PER CUBIC FOOT � <br /> C7Nt <br /> W= ■ 3, 360 LBS. TVP. <br /> ADJACENT TANKS <br /> 3. WEIGHTS 1N AIR <br /> MATERIAL WEIGHT 3. <br /> PEA GRAVEL 120 LBS. F'ER CUBIC FOOT FA ■ LUM + W. <br /> REINFORCED CONCRETE 150 LBS. PER CUBIC FOOT <br /> TYPICALTANK 23, 200 L55. SECTION <br /> DE$CRI PT I ON GALCULAT 1 ONS SUMMARY CALCUL AJ IONS <br /> FA ■ 48, 989 LBS. + 3, 360 LESS. <br /> I. REELECTED AREA : A = 10. 08 x 26. 08 = 263. 0 S. F. (1) F A ■ 57, 349 LBS. <br /> 2. DIaE _dr'ED VOLUM V = 700. 08)'/4 C. F. x 26. OS ■ 2, 081 C. F. <br /> „ <br /> 3. UPLIFT FORGE F u= 62. 4 LBS / C. F. x 2, 081 C. F. = 12Q, 868 LBS. (f) Fu = 129, 868 LBS. 4. FACTOR OF $AFETY WITH ANCHORS. <br /> 4. HOLD DOWN FORCES : F. 5.2= Fw + F" 159. 636 + 52, 34S , I. 63 OK <br /> Fu l29, 8(08 <br /> A) TANK WEIGHT (PER MFR SPECS.) W T 23, 200 LBS. (}) WT = 23, 200 LBS. <br /> B) 6' CONCRETE SLAB = 150. 00 LBS. / C. F. <br /> SLAB AREA A, _ ,4 , 12. 08 x 30. 08 = 363 51. F. <br /> SLAB WEIGHT EXCLUDING REINFORCEMENT W e ■ 150 x 363 x .50 ■ 21, 252 L55. (1) We ■ 21, 252 LBS. <br /> C) WEIGHT OF PEA GRAVEL OVERBURDEN VOLUME <br /> FROM CENTER OF TANK TO CONCRETE SLAB : <br /> (USE 5'-0' MIN. BURY DEPTH TO FINISH SURFACE <br /> 4'-6' TO SLAB BOTTOM WITH SUBMERGED WEIGHT V*= (H/3) (A, + A,+IA—,A,) - (0. 5VT + V.) <br /> OF PEA GRAVEL = 60 LBS. / C. F.) V.= (954/3) (263 + 363 + 2b x3 363 ) - ((0. 5 x 2, 081) + 113) <br /> OVERBURDEN VOLUME FROM CENTER OF TANK TO GONG. SLAB We= 1820 C. F. x 60 L55. / C. :R ■ 109, 184 LBS. (1) Wp = 109, 184 L55- <br /> VT <br /> BS.VT = VOL. OF TANK <br /> V m ■ VOL. OF MANWAY F„ = 23, 200 + 21, 252 + 109, I54 = 159, 636 L55. (j) F;, ■ 159, 636 LBS. <br /> TOTAL HOLD-DOWN FORGES : FH - (A + B + C) <br /> EHD■ F„- Fu a I59, bib - 129, 868 = 29, 168 LBS. (1) EHD = 29, 168 LBS. ".• rZ Lj • ' ,. <br /> 5. z OC <br /> E <br /> 6. FACTOR OF SAFETY EXCLUDINCs FRICT10N <br /> F. S., ■ " 159, 636 / 129, 868 = 1. 23 MARGINAL — <br /> 3 — —— _—— ———— '—-—-——————T —— -————`- — 1/4' x 3' HOT DIP GALVANIZED FLAT BAR HOLD DOWN STRAP 3 <br /> '1. CajQLUr2IQN. USE 6' TH1GKy 12. 08' x 32. 08' CONC. SLAB AND i A9 PROVIDED BY TANK MANUFACTURER BRUSH WITH <br /> TANK BURY DEPTH 5'-0' TO FINISH SURFACE I I F1BEW-CLASS RESIN, THEN WRAP WITH 30 MIL BLACK PIPE WRAP <br /> TAPE. INSTALL OVER 6' WIDE EPDM RUBBER ISOLATION STRAP. <br /> DUE TO SITE SPECIFIC VARIABLE$, BUOYANCY CALCULATIONS MUST I I (AVAILABLE FROM STEEL TANK INSTITUTE MEMBER TANK MANUFACTURERS) <br /> I I J <br /> BE CALCULATED FOR EAG+-•I INDIVIDUAL SITE BASED ON ACTUAL CONDITIONS, 1 <br /> I 1 1' DIA HOT DIP GALVANIZED ROUND BAR W / 12' LONG THREAD 4 2 NUTS <br /> 1 I AS PROVIDED BY THE TANK MANUFACTURER BRUSH WITH FI5ERGLA55 RESIN <br /> I I THEN WRAP WITH 30 MIL BLACK PIPE WRAP TAPE. <br /> I 1 <br /> GENERAL NOTES: DEAPtIEN / ANCNORINCz INSTALLATION <br /> I. 'T44%K ANCHORING SHALL BE INSTALLED ONLY WHEN 1. CONTRACTOR 15 TO INSTALL DEADMEN IN SUCH A MANNER <br /> APPROVED BY UNOCAL ENGINEER AND AS REQUIRED AS TO NOT REQUIRE PERSONNEL IN THE BOTTOM OF THE II \!'—!TWREAD FOOD ANCHORS ATTACHED t0 % REBARS TYPICAL OF ALL <br /> Br LOCAL AGENCIES. IT 18 REQ2j2N2r=0 THAT EXCAVATION. THESE INSTALLATIONS ARE INTENDED TO BE LOCATIONS. INSTALL WITH 'L' LECs UNDER REBAR 4 TIE-WIDE <br /> DURING TANK SETTING, CONTRACTOR MUST PROVIDE PROTECTION ON ENDS OF TANKS BE ANCHORED FOR INSTALLATIONS WHERE ONLY A GUIDE. CONTRACTOR nW COMPLY WITH ALL SECURELY IN PLACE <br /> I' ANCHOR BOLTS TO ELIMINATE THE POSSIBILITY OF DAMAGING THE FRP COATING CID WATER IS LESS THAN 16 FEET BELOW GRADE. APPLICABLE OSHA OR GAL/OSHA REGULATIONS. 10+_0■ 5'_h' 10'-0' <br /> OF THE TANK. PROTECTION MAY CONSIST OF P HOSE OR REBAR PROTECTIVE 2. FO'R HOLD-DOWN STRAP LOCATIONS, REFER TO 2. CONCRETE DEADMEN SHALL BE PRECAST ABOVE GRADE WITH <br /> CAPS AND PIPE WRAP TAPE AT CONTRACTOR'S OPTION- IN ADDITION, IF TANK DETAIL HEREON. ANCA-10R RODS IN PLACE, ON CENTERS (AS SHOWN), A MINIMUM <br /> EXCAVATION 15 APT TO FILL WITH WATER FROM AbY SOURCE, TANK IS TO BE OF 1 DAYS PRIOR TO INSTALLATION g _@• 8,_ <br /> BALLASTED WITH CLEAN WATER AT NO TIME IS BALLAST WATER LEVEL IN TANK 3. 50'm GALLON WASTE OIL LANK, WHEN INSTALLED MODERN <br /> PER UNOCAL STANDARD PLANS AND 5PECIFiCATIONS, 3. PROPERLY POSITION DEADMEN IN THE HOLE (ON TOP OF <br /> TO EXCEED LEVEL OF WATER COR BACKFILL) IN TANK EXCAVATION. AFTER YIELDS A SAFETY FACTOR OF 3. 62 : 1, THEREFORE FILTER FABRIC) PRIOR TO ANY BACKFILL- WELDING Y j�!y <br /> INSTALLATION, ALL WATER 15 TO BE REMOVED BY PUMPINCs WITH SUCTION HOSE AT NO SUPPLEMENTAL ANCHORS ARE REQUIRED- <br /> LOW END OF TANK AFTER WATER IS REMOVED, CIRCULATE DRY COMPRESSED AIR 4. PLACE A 12' THICK BED OF PEA G=RAVEL AND GRADE SMOOTH. h <br /> T ROAJCsH TANK OPENINGS t0 DRY LANK INTERIOR ALL TANK OPENINGS MUST 8E 4. SHORING WILL BE REQUIRED FOR ALL PROJECTS <br /> Na. <br /> LEFT OPEN DURING THIS DRYING OPERATION,. CONTRACTOR MUST PROVIDE REQUIRING ANGHORINCs. (ALL WET HOLE CONDITIONS) 5• SET TANKS ON PEA GRAVEL BED. <br /> CERTIFICATION THAT THE TANK WAS DRIED COMPLETELY AND 15 CLEAN. DO NOT b. BACKFILL TO CENTERLINE OF TANKS. oF <br /> USEI T TY A 1N T rAAIFOAN <br /> 1. POSITION ANCHOR STAPS AND ATTACH TO ANCHOR RODS. <br /> TIGHTEN TO OBTAIN A SNUG FIT, <br /> 8. BACKFILL TO TOP OF TANK <br /> 4 ' of=STRar AL PRCNTs �• �D• �''D � APPROVAL RECORD <br /> APPROVALS <br /> UNION OIL OF CALIFORNIA, dba UNOCAL, 994 REv DATA 1 REVISED BEARING EARLIER DATE �r BY er 11 <br /> MILESTONE DATE APPROVAL DRAWN BY TAIT <br /> THIS DOCUMENT AND THE INFORMATION CONTAINED HEREIN IS ISSUED FOR C.U.P. UNDERGROUND GASOLINE STORAGE TANK COUNTER <br /> PROPRIETARY TO UNION OIL OF CALIFORNIA (UNOCAL) AND HAS CHECK® BY WD BUOYANCY DETAILS AND CALCULATIONS <br /> BEEN FURNISHED IN CONFIDENCE AND ARE SUBJECT TO THE ISSUED FOR PLAN CHECK <br /> TERMS OF A SEPARATE SECRECY AGREEMENT BETWEEN UNOCAL APPROVED <br /> AND THE RECIPIENT. THE RECIPIENT IS NOT TO COPY, DUPLICATE — ISSUED FOR GEN. BID <br /> OR DISCLOSE THE CONTENTS TO ANY PERSON OR ENTITY EXCEPT 2.-.8-95 ( ) a DRAWING NO. REV NO. <br /> AS EXPRESSLY AUTHORIZED BY SAID AGREEMENT OR BY UNOCAL 1ssuED FOR CONSTRUCT. UNOCAL* <br /> I <br /> SHEET <br /> IN WRITING. -- RECORD DRAWING scAlf NOME I f,4NER) <br /> ! � sAArirs <br /> A B C p <br /> F K:\UN\UN16$2\JDWGS\STD—J-6 <br />