Laserfiche WebLink
Veeder-Root R <br />Issue Date: November 22, 1995 <br />Revision Date: September 3, 2002 <br />Veeder-Root <br />rage t or z. <br />ILS -350, TLS -300C, 3001, 300PC, 350, 350PC, 350R, 350RPC, Red Jacket ProMax and ProPlus <br />with Solid -State Pan/Sump Sensor 794380-321, 351, <br />Piping Sump Sensor 794380-208, 209, <br />Micro Sensor 794380-340 <br />INTERSTITIAL DETECTOR (LIQUID -PHASE) <br />Detector: <br />Output type: qualitative <br />Sampling frequency: continuous <br />Operating principle: product permeable, ultrasonic/float switch <br />Test Results: <br />unleaded gasoline <br />diesel <br />water <br />Solid -State Pan/Sump Sensor 794380-321, <br />351 <br />Minimum product thickness (cm) <br />2.60 <br />2.50 <br />2.60 <br />Precision (cm) <br />0.010 <br />0.010 <br />0.010 <br />Detection time (sec) <br /><1 <br /><1 <br /><1 <br />Piping Sump Sensor 794380-208, 209 <br />Minimum product level (cm) <br />3.51 <br />3.40 <br />3.03 <br />Precision (cm) <br />0.011 <br />0.011 <br />0.011 <br />Detection time (sec) <br /><1 <br /><1 <br /><1 <br />Micro Sensor 794380-340 <br />Minimum product thickness (cm) <br />0.51 <br />0.46 <br />0.48 <br />Precision (cm) <br />0.011 <br />0.007 <br />0.007 <br />Detection time (sec) <br /><1 <br /><1 <br /><1 <br />Comments: <br />Sensors are reusable. <br />208 and 209 sensors are also compatible with 300 series. <br />Veeder-Root <br />125 Powder Forest Dr. <br />Simsbury, CT 06070-2003 <br />Tel: (860) 651-2700 <br />E-mail: dhalla@veeder.com <br />URL: www.veeder.com/dynamic/index.cfm <br />Evaluator: Ken Wilcox Associates <br />Tel: (816) 443-2494 <br />Dates of Evaluations: 10/20/94, 05/22/02 <br />http://www.nwglde.org/evals/veeder_root_r.html 6/13/07 <br />