Laserfiche WebLink
m _r. <br /> Leak Detection System Notes <br /> SUMP LID 1. WARNING: <br /> MANHOLE C-H GRFX WITH MONITOR SENSOR & PROBE WIRING IS INTRINSICALLY SAFE WIRING AND MUST BE <br /> 2 CORD GRIP COVER AND GASKET SEPARATED FROM ALL OTHER WIRING AND INSTALLED IN SEPARATE CONDUIT. ' <br /> SLAB WEATHERPROOF MAXIMUM CABLE LENGTH BETWEEN MONITOR CONSOLE AND SENSORS IS 1,000 FEET. " <br /> SEALS SUPPLIED JUNCTION BOX <br /> 18" DIA. MANHOLE 12 WITH SENSOR 2. WARNING: <br /> (TYP.) <br /> TO MAINTAIN INTRINSIC SAFETY, THE JUNCTION BOX MUST <br /> 3/4" CONDUITCONTAIN ONLY WIRE SPLICES. <br /> J—BOX 3. CAUTION: BErIR <br /> SEAL OFF 4 a °o' ° 120 VAC WIRING MUST NOT BE CONNECTED TO LOW VOLTAGE <br /> TO LEAK DETECTION MONITOR o EPDXY SEAL CONNECTIONS. DAMAGE FROM MISWIRING IS NOT COVERED BY <br /> PANEL 2 CONDUCTOR #18 a ° ° a ° PER NFPA WARRANTY. INSTALLING CONTRACTOR TO BE HELD RESPONSIBLE. <br /> SHIELDED CABLE IN RIGID ° a SPEC 4. INSTALL TANK MONITOR SYSTEM PER MANUFACTURER'S INSTALLATION <br /> METAL OR PVC SCH. 40 - INSTRUCTIONS. nr' <br /> TO LEAK DETECTION 5. HAA <br /> NOB CONDUIT. SEAL—OFF z MONITOR PANEL 2 5. INSTALL METAL CONDUIT OR RACEWAY FOR MONITOR CONSOLE POWER FROM <br /> 2 WIRE SHIELDED CABLE 2 WIRE CABLE CONDUCTOR #18 THE POWER PANEL TO THE MONITOR CONSOLE LOCATION. CONDUIT MUST — FOODS <br /> SHIELDED CABLE IN RIGID ALIGN WITH THE DESIGNATED POWER KNOCKOUT. <br /> 4" API PIPE <br /> SCHEDULE 40 METAL OR PVC SCH. 40 6. RUN RIGID METAL CONDUIT FOR PROBE AND SENSOR WIRING FROM <br /> FRP PIPE OPEN I 4 DIA. PVC PIPE, CONDUIT. THE MONITOR CONSOLE TO THE LOW VOLTAGE WIREWAY. CONDUIT MUST <br /> AT BOTTOM, ATTACHED i SCH. 40 ENTER THE MONITOR WHERE KNOCKOUTS ARE PROVIDED. NO OTHER CONDUIT )A� l <br /> TO SUMP WALL I 2 1 g� 2 4 <br /> ( ) ( ) ENTRY IS PERMITTED. ALWAYS KEEP PROBE AND SENSOR WIRING IN A SEPARATE X „ <br /> PROVIDE SPACER, AND I GND CLAMPS W/ CONDUIT OR WIREWAY FROM ALL OTHER WIRING. 4 <br /> FIBERGLASS BOTH PIPE I 1 " RIGID CONDUIT TO #6 BARE SOLID 7. ALL U.G. CONDUIT FOR SUBMERSIBLE PUMP POWER, <br /> AND SPACER TO iGILBARCO DISPENSER POWER OR DATA WIRING SHALL BE PVC COATED RIGID <br /> I %MAGNETOSTRICTfVE <br /> ATG CONDUIT MAY BE PVC SCHEDULE 40 IF WIRING IS APPROPRIATELY UPGRADED <br /> SUMP - AND CONDUIT IS BURIED AT 24" MINIMUM. ALL FITTINGS AND THE FINAL 24" TO 500 WEST CAPITOL AVENUE <br /> PROBE ANY LOCATION SHALL BE PVC COATED RIGID GALVANIZED. WEST SACRAMENTO, CA <br /> 8. WIRING BETWEEN PROBES, SENSORS AND THE MONITOR CONSOLE IS DESIGNED <br /> DO NOT NOTCH COLLAR I SUCH THAT ELECTRICAL POWER TO THE PROBE AND SENSOR WIRE IS <br /> 95605 <br /> BRINE HYDROSTATIC LIMITED SO THAT THERE IS INSUFFICIENT ENERGY PRESENT TO IGNITE P.O. BOX 15618 SACRAMENTO, CI <br /> VEEDER ROOT 34 RESERVOIR • THE FUEL. TO MAINTAIN THIS SAFETY FEATURE, PROBE AND SENSOR <br /> LIQUID SENSOR WIRES MUST BE INSTALLED IN SEPARATE CONDUITS FROM ALL OTHER 95852 <br /> APEX OF 1 FIBERGLASS TANK WIRING. NEVER RUN THESE WIRES IN THE SAME CONDUIT OR WIRING. REVISIONS <br /> TANK TROUGH AS POWER WIRES. . <br /> 1" MAX. FROM BOTTOM OF SUMP AND 9. INSTALL A WEATHERPROOF ELECTRICAL JUNCTION BOX WITH <br /> LOCATED AT SIDE OF PRODUCT LINE GASKETED COVER ON THE END OF EACH CONDUIT RUN AT THE PROBE <br /> ENTRY BELOW LEVEL OF BOTTOM OF _ AND SENSOR LOCATIONS. GASKEfING OR SEALING COMPOUND MUST =° <br /> LOWEST PENETRATION FITTING. BE USED AT EACH ENTRY TO THE JUNCTION BOX TO ENSURE A ; /® <br /> WATERPROOF JUNCTION. /L <br /> 10. PULL TWO CONDUCTOR 100% SHIELDED CABLE, THWN <br /> DUAL FLOAT BETWEEN THE MONITOR CONSOLE AND EACH PROBE AND <br /> HYDROSTATIC SENSOR 38 SENSOR LOCATION. SINCE UP TO THREE PROBES AND FIVE <br /> FIBERGLASS TANK SENSORS WILL BE WIRED THROUGH THE CONDUIT, BE SURE TO USE A <br /> (TYP.) DIFFERENT COLOR CODE FOR EACH CONNECTION. LABEL OR COLOR <br /> ALL FIELDED WIRING TO ENSURE POLARITY. <br /> 11. THE INSTALLATIONS SHALL COMPLY WITH THE NATIONAL ELECTRICAL <br /> CODE; FEDERAL, STATE AND LOCAL CODES; AND OTHER APPLICABLE <br /> Permanently Mounted Liquid Sensor SAFETY CODES. <br /> at T u r b i n e a n d F i I .1S u m p s H d r o s t �tii M o�niior Detail Tank Gauging I n s t a I I a t I O n 12. OFTHELEAK DETECTION SYSTEM WILLINTERRUPT ALLANY POWERTO THE G H A <br /> PRODUCT PUMPS. S <br /> 1 NOT TO SCALE: NOT TO SCALE: 5 �P FZ <br /> 13. CERTIFIED INSTALLERS- ALL MANUFACTURERS TRAINING REQUIREMENTS SHALL BE <br /> MET BY CONTRACTOR INSTALLING PROBES AND WIRING TO MONITORING SYSTEM <br /> AS WELL AS DISPENSER WIRING. <br /> EQUIPMENT SCHEDULE <br /> (TYP.) 2 14. IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO NOTIFY THE err � _ <br /> O GROUND ROD VEEDER ROOT DISTRIBUTOR FOR STARTUP. G �' <br /> INSTALL OUTSIDE ITEM 15. SEE MANUFACTURERS WIRING DIAGRAM FOR SPECIFIC WIRING 9 `T/NG ENG�N��� <br /> OF TANK 0 DESCRIPTIONAND FURTHER INFORMATION. WIRE THE EQUIPMENT AS « <br /> EXCAVATION IN NO. REQUIRED BY THE MANUFACTURERS WIRING DIAGRAMS. 4 < <br /> NATIVE SOIL o TURBINE SIDE "LAND PLANNING AND DESIGN SPECIALISTS" <br /> o SUMP (TYP.)) 1/2" 0 X 10' LONG COPPERBONDED GROUND 16. EACH TURBINE RELAY IS TO BE WIRED INTO THE MONITOR CONTROL 18215 72ND AVENUE SOUTH <br /> SO THAT At ACTIVATION OF TURBINE SIDE SUMP PROBE OR ANNULAR SPACE KENT, WASHINGTON 98032 <br /> 3 <br /> 91 OCTANE O ROD: "ERICO" PART NO. 611300 (UL LISTED) PROBE WILL ,MUT DOF"9: THE TURBINE FOR THAT TANK. (425) 251 -6222 <br /> 4 UNLEADED OR EQUIVALENT 17. DENOTES EQUIPMENT ON BOND GROUND WIRE SHEET TK8-1 <br /> (TYP.) PREMIUM #4 AWG STRANDED BARE COPPER GROUND SHEET TITLE <br /> OTO ALL METALLIC WIRE. PROVIDE TERMINAL CONNECTORS AT <br /> RISERS AS REQUIRED U-BOLT CONNECTIONS GROUNDING, <br /> (TYP.) SEE BONDING <br /> DETAIL CADWELD #4 WIRE CABLE TGROUND ROD <br /> #4 STRANDED AWG MONITORING <br /> CONNECTION "ERICO" PART- N N0. GTT14A1 L, USE <br /> TERMINAL CONNECTION 87 OCTANE FILL IDE SUMP WELD METAL #32 AND SENSOR <br /> UNLEADED TYP. CADWELD `T CONNECTION FOR #4 BARE DETAILS <br /> 5 (TYP.) O STRANDED WIRE CABLES. "ERICO PART NO. <br /> 4 <br /> (TYP.) 2 TAC1 L1 L, USE #32 WELD METAL. <br /> CADWELD "L" CONNECTION FOR #4 BARE <br /> 7 <br /> (TYP.) 6 (TYP.) O STRANDED WIRE CABLES TO 3/4" BRONZE <br /> DIESEL STUD. "ERICO" PART NO. GRC181 L, USE #90 <br /> WELD METAL. BCE #12004 <br /> ANCHORING PLATE o ��o 4 NPT ADJUSTABLE BRONZE PIPE CLAMP, <br /> (:000 <br /> o LIND EQUIPMENT P/N JR-150-30 (905) <br /> 475-5086 <br /> 4" DIA. BRONZE 6 RISER (TYP.) PROJECT NAME <br /> GROUND CLAMP <br /> (TYP.) O ACCESSO/0 EROPW 6110-12WT 12'° H-20 RATED RALE I 'S <br /> BRONZE <br /> Bonding D e t a i ( P l a n View O STUD BIOLIT W/ BRONZEETER x 4" ONNU SOLID AND WASHERS. #356 <br /> NOT TO SCALE: NOT TO SCALE: <br /> Ii TANK TANK <br /> 2 (TYP.) I 4 (TYP.) BOXT(IINNMFNT FINISH <br /> SURFACE <br /> _ <br /> 4" BLACK STEEL AGE ROA <br /> FILL PIPE (TYP.) i #4 STRANDED BARE 2 ��'•� MORADALANE <br /> /i ! COPPER GROUND STOCKTON, CALIFORNIA <br /> 5 TO GROUND CLAMPS <br /> (TYP.) CONTAIN ME)T I EXTERNAL SUMP WALL ON FILL RISERS 11 PROJECT NO. <br /> SUMP TYP.) 2.3208.000 <br /> 6 #4 STRANDED 2 TERMINAL I <br /> (TYP.) �// I BARE COPPER CONNECTION <br /> DRAWN BY <br /> 4jDOUBLE WALL GROUND (TYP.) <br /> TANKS TO OTHER TANKS j <br /> v #4 STRANDED BARE 2 <br /> 2 PEAGRAVEL CRUSHED COPPER GROUND 8 3/4"0 x 4" LONG SOLID BRONZE <br /> COIL STATIC / SCALE <br /> CABLE UP 3' & ROCK BACKFILL TO GROUND ROD STUD BOLT, ALL THREADED W/ <br /> SECURE TO SIDE WASHERS AND NUTS. BED BOLT IN AS SHOWN <br /> OF BLACK STEEL I <br /> RISER CAULKING OR PTI PASTE (TYP.) <br /> I Q FESSIO& ` <br /> "T" CADWELD #4 ¢ DRILL 7/8'° HOLE IN SUMP WALL (TYP.) q� DATE <br /> EARTH I 7 HAL P.G 8 2 23 JUNE 2005 <br /> I STRANDED BARE I m m <br /> (GROUND ROD INSTALLED IN SOIL NOT PEAGRAVEL/CRUSHED ROCK BACKFILL) COPPER WIRE 6s <br /> i INSTALL FIBERGLASS MAT AND GLASS RESIN i <br /> CONNECTION <br /> BOLT, WASHERS AND FIRST SET OF NUTS N.� 310 �r PAGE NO. <br /> #4 STRANDED BARE COPPER 5 TO SUMP BOTH SIDES (TYP.) crvl� ' / <br /> Typical Static Grounding Detail `\ GROUND TO 3/4" 0 STUD BOLT ttt6 <br /> CADWELD "L" CONNECTION INTERNAL <br /> TK7-4 <br /> 2 (TYP.) <br /> NOTTO SCALE: -------------------------------------------------------------------------------------------------------------------------------------- <br /> TYPICAL PENETRATION & CONNECTION DETAIL <br /> (SEE INSTALLATION SEQUENCE NOTES BELOW) „' SHEET OF <br />