SWRCB,January 2002 *ft.� ../ Page 4. <br /> 7. UNDER-DISPENSER CONTAINMENT (UDC)TESTING <br /> Test Method Developed By: F-1 UDC Manufacturer Industry Standard ❑X Professional Engineer <br /> Other (Spec) <br /> Test Method Used: Pressure Vacuum Hydrostatic <br /> Other (Specify) <br /> Test Equipment Used: vpt1 Equipment Resolution: inches <br /> UDC# 1/2 UDC# 3/4 UDC# UDC# <br /> UDC Manufacturer: bravo bravo <br /> UDC Material: fiberglass fiberglass <br /> UDC Depth: 30" 30" <br /> Height from UDC Top to Top of 11" 11" <br /> Highest Piping Pentration: <br /> Height from UDCTop to Lowest 31- 311 <br /> Electrical Pentration: <br /> Condition of UDC prior to testing: good good <br /> Portion of UDC Tested: t 13" 1311 <br /> Does turbine shut down when <br /> sump sensor detects liquid(both flYes❑Na❑N Yes❑No�N Yes❑No❑N Yes�No�I <br /> product and water)?* <br /> Turbine shutdown response time: 2-5sec 2-5sec <br /> Is system programmed for fail-safe ❑ fl � ❑ ^ [:]Yes <br /> ❑ ^ ❑ ❑ <br /> shutdown?* Yes N N Yes R oUN Yes NouN Yes NoE]N <br /> Was fail-safe verified to be ❑ � ❑ �� ❑ ❑ ❑ ❑ R_ <br /> operational?* Yes N N Yes R Yes X N N Yes No <br /> Wait time between applying <br /> pressure/vacuum/water and starting 5min 5min <br /> test: <br /> Test Start Time: 9:42 9:31 <br /> Initial Reading(Rt): 0 0 <br /> Test End Time: 9:57 9:46 <br /> Final Reading(RF): -.0003" -.0006" <br /> Test Duration: 15min 15min <br /> Change in Reading(R F-RI ): -.0003" -.0006" <br /> Pass/Fail Threshold or Criteria: -. 002" - . 0 02" <br /> Test.R t: ` ❑ Fail Pass El Fail 0 <br /> Was sensor removed for testing'? E1yesE]N,0NA E]YesENo❑NA Yes N NAYes No <br /> Fl <br /> Was sensor properly replaced and <br /> verified functional ager testing? ❑Ye X N�A ❑Ye X NcE] ❑NA YeC]NcE]N A❑Yes❑N <br /> Comments - (include information on repairs made prior to testing, and recommended follow-up forfailed tests) <br /> I If the entire depth of the UDC is not tested,specify how much was tested.If the answer to-any-of the questions indicated with an <br /> asterisk(*)is "NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />