Laserfiche WebLink
Triangle Environmental, Inc. <br /> 2525 West Burbank Blvd.,Burbank,CA 91505-2302 <br /> (818)840-7020 (818)840-6929 <br /> UST TESTING SYSTEMS SUMMARYSHEET <br /> Precision Underground Storage Tank System Leak Test <br /> Client: <br /> Conoco Phillips Co. Facility # 2701205 <br /> 1500 North Priest Drive <br /> Tempe, AZ 85281 Test Date: 6/ 5/03 <br /> Kathy Strickland <br /> (602)728-7149 01205 <br /> Fatality: 2701205 Work#: 20001100 <br /> Facility#2701205 County: SAN JOAQUIN <br /> 16470 CAMBRIDGE Cross Street: NEC LOUISE AVE/CAMBRIDGE <br /> LATHROP, CA 95330 <br /> Tank Test System Tank Line <br /> # Product Capacity Type Rate/Resuns Ullage Result Rate/Result LID Ranh <br /> 1 Unleaded Regular 11849 System 4000 N/A N/A 0.005 PASS PASS <br /> 2 Unleaded Premium 11849 System 4000 N/A N/A 0.005 PASS PASS <br /> Certified By: Technician: Tom Corcoran State Lic.#s: 02-1626 <br /> Mfgr's#: TEI-067 <br /> VR-7539 <br /> Comments: <br /> Compliance P-L/TST&monitor certification.Monitor certification failed due to 91 annular sensor being <br /> broken. <br /> This precision tank testing system has been third party evaluated according to the guidelines of the EPA <br /> procedures for annual leak detection systems and found to exceed the criteria of detecting a leak of 0.10 <br /> gph with a Pd>95% and Pfa<5%as required by Local,State and Federal EPA UST Technical <br /> Standards Part 280 for precision testing systems. This SB-989 secondary containment testing system <br /> exceeds the criteria for detection as required by state and local agencies. <br /> UPS result to Roseville <br />