Laserfiche WebLink
Triangle Environmental Inc <br /> 2525 West Burbank Blvd.,Burbank,CA 91505-2302 <br /> (818)840-7020 (818)840-6929 <br /> UST TESTING SYSTEMS SUMMARYSHEET <br /> Precision Underground Storage Tank System Leak Test <br /> Client: <br /> Marketing Co. <br /> 1500 North Priest Drive <br /> Tosco Facility # 01205 <br /> 1500 <br /> Tempe, Az sszsl <br /> Kathy Strickland Test Date 7/16/2001 <br /> (602)728-7149 <br /> Facility: 2701205 Work#: 7405410 <br /> Tosco Facility# 01205 County: SAN JOAQUIN <br /> 16470 CAMBRIDGE Cross Street: LOUISE AVE <br /> LATHROP, CA 95330 <br /> Tank Test System Tank Line <br /> # Product Capacity Type Rate/Resifts llag; Result Rate/Result L/DResult <br /> 1 Unleaded Regular 11849 N/A N/A 0.000 PASS PASS <br /> 2 Unleaded Premium 11849 N/A N/A 0.000 PASS PASS <br /> Certified By: Technician: Steve Sweatt State Lic.#s: CA-1616 <br /> Mfgr's#: TEI-056 <br /> 70-17 <br /> Comments: <br /> / <br /> Compliance UD&monitor certification <br /> This precision tank testing system has been third party evaluated according to the guidelines of the EPA <br /> procedures for annual leak detection systems and found to exceed the criteria of detecting a leak of 0.10 <br /> gph with a Pd>95%and Pfa<5%as required by Local,State and Federal EPA UST Technical <br /> Standards Part 280 for precision testing systems. <br />