Laserfiche WebLink
..i <br /> Triangle Environmental Inc <br /> 2525 West Burbank Blvd., Burbank, CA 91505-2302 <br /> (818) 840-7020 (818)840-6929 <br /> UST TESTING SYSTEMS SUMMARY SHEET <br /> Precision Underground Storage Tank System Leak Test <br /> Client: <br /> Tosco Marketing Co. <br /> 1500 North Priest Drive TOSCO Facility # 01205 <br /> Tempe, AZ 85281 Test Date: 7/16/2001 <br /> Kathy Strickland <br /> (602)728-7149 <br /> Facility: 2701_ Work#: 7405410 - <br /> Tosco Facility # 0120 County: SAN JOAQUIN <br /> 16470 CAMBRIDGE Cross Street: LOUISE AVE <br /> LATHROP A 30 <br /> Tank Test System Tank Line <br /> 0 Product Capacity Type Rate/Results Ullage Result Rate/Result LID Result <br /> 1 Unleaded Rel;ular 1 1849 N/A N/A 0.000 PASS PASS <br /> 2 Unleaded Premium 11849 N/A N/A 0.000 PASS PASS <br /> Certified By: Technician: Steve Sweatt State Lic. #s: CA-16.e <br /> Mfgr's#: TEI-056 <br /> OJT. <br /> Comments: <br /> Compliance L/D& monitor certification <br /> This precision tank testing system has been third party evaluated according to the guidelines of the EPA <br /> procedures for annual leak detection systems and found to exceed the criteria of detecting a leak of 0.10 <br /> gph with a Pd>95%. and Pfa<5% as required by Local,State and Federal EPA UST Technical <br /> Standards Part 280 for precision testing systems. This SB-989 secondary containment testing system <br /> exceeds the criteria for detection as required by state and local agencies. <br />