Laserfiche WebLink
Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Circle K #01205 <br /> Tank #: 3 Test Date: 4/28/97 <br /> Product: Unleaded Premium wore:#: 460016 <br /> Lr` _TANK TEST RES ULT ; LEA® 'TECTORTEST_RFSULfi`:` <br /> Test Method: System 5000 Test Method: R.J.FTA <br /> Capacity: 4006 Manufacturer: Red Jacket <br /> Diameter(in): 76 L/D Model: DLD <br /> Product Level(in): 49 L/D Serial#: 404489-9803 <br /> Liquid Volume(Gals): 2730 Line Drain Back(ml): 50 <br /> Liquid Percent(%): 68.1% L/D Trip Time(sec): 2 <br /> Specific Gravity: 0.750 Holding Pressure(psi): 20 <br /> Coef.of Expansion: 0.000650 Metering Pressure(psi): 24 <br /> Water On Tank(in): 0 L/D Test Rate(gph): 2.2 <br /> Water In Tank(in): 0 L/D Result: PASS <br /> Product Temp. (F): 67 <br /> Head Pressure(psi): 1.3 .�.. <br /> -m, � >Ji EST RESU <br /> Test Start Time: 9:15:00 PM <br /> Test End Time: 9:30:00 PM Test Method: TEI LT-3 <br /> Test Rate(gph): 0.02 Pump Brand: Red Jacket <br /> Test Result: PASS System Type: Pressure <br /> Line Pressure(psi): 50 <br /> OEM Line Start Time: 8:30:00 PM <br /> Test Method: ULLAGE Line End Time: 8:45:00 PM <br /> UllageVolume(gals.): 1276 <br /> Line Start Level: 270 <br /> Ullage Test Time: 9:15:00 PM Line End Level: 260 <br /> Ullage Vacuum(psi): 1.8 '� <br /> Line Test Rate(gph): 0.010 <br /> Ullage Result: PASS Line Test Result: PASS <br /> 2 <br />