Laserfiche WebLink
Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Circle K #01205 <br /> Tank A. 2 Test Date: 10/ 9/96 <br /> Product: Uhleaded'Regular Werk#: 30'079 <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: 9980 7MM Manufacturer: Red Jacket <br /> Diameter(in): L/D Model: XLD <br /> Product Level(in): L/D Serial#: 30295-9354 <br /> Liquid Volume(Gals): Line Drain Back(ml): 90 <br /> Liquid Percent(%): L/D Trip Time(sec): 3 <br /> Specific Gravity: Holding Pressure(psi): 10 <br /> Coef.of Expansion: Metering Pressure(psi): 12 <br /> Water On Tank(in): L/D Test Rate(gph): 1.3 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): <br /> Head Pressure(psi): <br /> Test Start Time: <br /> Test End Time: Test Method: TO LT-3 <br /> Test Rate(gph): Pump Brand: Gilbarco <br /> Test Result: N/A System Type: Pressure <br /> Line Pressure(psi): 50 <br /> Line Start Time: 9:50:00 PM <br /> Test Method: ULLAGE Line End Time: 10:05:00 PM <br /> UllageVolume(gals.): Line Start Level: 315 <br /> Ullage Test Time: Line End Level: 300 <br /> Ullage Vacuum(psi): Line Test Rate(gph): -0.015 <br /> Ullage Result: N/A Line Test Result: PASS <br /> Replaced UNL leak detector <br /> 3 <br /> a <br />