Laserfiche WebLink
Tr- ia"ole 3. roriM4-- l Inc . <br /> 517 East Wilson Ave. , Glendale, CA 91206 (818) 246-2464 <br /> -re: I S Y S T E M 4 0 0 0 S U M M A R Y SHE E T <br /> Precision Underground Storage Tank System Leak Test <br /> W C3# N 1 5 4 3 <br /> Client: CIRCLE K CORP. <br /> 6101 N. SIERRA AVE . <br /> FONTANA, CA. <br /> Date: 9-29-92 <br /> OCT 6 11 X19 County : SAN JOAGIN <br /> Site: CIRCLE K #1205 <br /> 16470 CAMHRIDE <br /> LATHROP, CA. i ... <br /> Tank Product Tank Tank/Lines Product Line Leak <br /> # Description Capacity Rate/Result Rate/Result Detector <br /> ------------------------------------------------------------------------ <br /> 1 UNLEADED 10000 +0.027 PASS -0.002 PASS PASS <br /> 2 UNL-PLUS 10000 -0.035 PASS -0.005 PASS PASS <br /> 3 PREMIUM 10000 +0.011 PASS -0.000 PASS PASS <br /> 4 <br /> 5 <br /> 6 <br /> Signature: ( i�l State License #: 90-1072 <br /> Technician Name: J , RICH <br /> Date: 9- 92 <br /> Comments: <br /> This precision tank testing system exceeds the criteria required by <br /> Local , State and Federal NFPA #329 and EPA UST Technical Standards Part <br /> 280 for precision testing systems. <br />