Laserfiche WebLink
E <br /> N March 30 , 1987 <br /> V Circle K Corporation <br /> 1 5811 Manzanita Avenue <br /> R Carmichael , California 95608 <br /> 0 P Attn: Pat Wright <br /> N <br /> M B RE : Petro-Tate Tank Test <br /> E o <br /> N X Dear Pat: <br /> T 2 On March 20 1987 we <br /> s , performed a Petro-Tite Tank Test <br /> A 0 <br /> at Store # 1205 - 16470 Cambridge Street , Lathrop, California. <br /> L 6 The test was performed by Robin Olson , E .P . E . Technician . <br /> The NFPA code 329.02 criteria for a tight tank system is a <br /> S tolerance of . 050 gallons per hour. Because of the almost <br /> P T infinite variables involved , this is not intended to be a <br /> p mathematical tolerance and is not the permission of actual <br /> E <br /> E K leakage. <br /> R 0 PRECISION TANK TEST <br /> O N <br /> L Tank 2 -East <br /> E C Size - 10,000 gallons <br /> V A Product - Unleaded <br /> M 9 The test showed a positive . 023 gallons per <br /> 5 hour. Based on the above criteria , we find <br /> 2 the tank system tested mathematically tight . <br /> 0 <br /> E This concludes our tesst and findings on March 20, 1987 . <br /> N ^ If you have any questions regarding the results, please con- <br /> G 2 tact me . An extra copy has been included for you to notify <br /> 0your local County Health Department, Environmental Health. <br /> N 9 If you have any questions on what your next step should <br /> E s be, please contact your local Health Department immediately. <br /> a <br /> E 3 Sincerely, <br /> R <br /> I o <br /> N 2 <br /> G 2 Robin Olson <br /> Certified Tank Testing Technician <br /> I <br /> N RO/bm <br /> C Encl . <br />