Laserfiche WebLink
STOCKTON SERVICE STATION EQUIPMENT C991bkT} _2 PH 2. 00 <br /> 808 N. UNION STREET <br /> STOCKTON, CA 95205-4152 SAEVcOUN YNIRONME <br /> PHONE 209.464.8333 FAX 209.464.8349 HEALTH DEPARTMENT <br /> LDT-890 LEAK DETECTOR TEST RECORD <br /> CUSTOMER: Country Market Place DATE: May 24,2005 <br /> LOCATION: 1789 W. Charter Way <br /> CITY: Stockton STATE: CA ZIP:95206 <br /> TECHNICIAN: MIKE JONES <br /> Submersible Pump Identification- <br /> Manufacturer Model Serial Number <br /> REDJACKET <br /> Leak Detector Identification <br /> Manufacturer Description Other Style Leak Detector <br /> 87 OCTANE <br /> REDJACKET <br /> Diaphragm-type <br /> Piston-type X <br /> Leak Detector in Submersible Pump <br /> Test at Dispenser <br /> 1. Operating Pump Pressure 27 psi (Purging Test System) <br /> 2. Gallons per hour rate 3 Gallon (Leak Test,Phase I) <br /> 3. Line pressure with pump shut off 10 psi (Leak Test Phase 1) <br /> 4. Bleed-Back Test with pump off 150 ml (Bleed-back Test) <br /> 5. Step-through time to full Bow 2 seconds (Step-through Time) <br /> 6. Leak detector stays in leak search position. (Leak Test Phase II)Yes X No <br /> LEAK DETECTOR TEST <br /> Note: Pass=Leak detector fits test protocol <br /> Fall =Leak detector fails test protocol <br /> Pass X <br /> Fail <br /> Form 890C <br />