Laserfiche WebLink
VAPORLESS MANUFACTURING, INC. <br /> LDT-890 Leak Detector Test Record <br /> Contractor Customer <br /> DIALYSIS NORTH COUNTRY MARKET PLACE <br /> Date Location Product <br /> 4-5-04 9 -,0. Ch a r-itr UOCU(4, 91 <br /> Technician <br /> GREG HARTMAN LIC#03-1640 <br /> Submersible Pump Identification <br /> Manufacturer Model No. Serial Number <br /> RED JACKET 91-P15151 91-1001-409%4942 <br /> Leak Detector Identification <br /> Manufacturer Description Other Style Leak Detector <br /> RED JACKET 91-012397-1861 FXIV <br /> Diaphragm-type <br /> Piston-type X <br /> Lesk Detector in Submersible Pump <br /> Test at Dispenser <br /> I. Operating Pump Pressure 28 psi (Purging Test System) <br /> 2. Gallons per hour rate 3 (Leak Test Phase 1) <br /> 3. Line pressure with pump shut off 13 psi (Leak Test Phase 1) <br /> 4. Bleedback Test with pump off 205 ml (Bleed—back Test) <br /> 5. Step-through time to full flow 5.76 seconds (Step-through Time) <br /> 6. Leak detector stays in leak search position. (Leak Test Phase 2) Yes X No <br /> LEAK DETECTOR TEST <br /> Note: Pau=Leak detector stays in slow-flow during GPH test <br /> Fail=Leak detector steps through to allow full pump pressure during GPH test <br /> Pass X <br /> Fail <br /> 'Complete thermal expansion test before failing leak detector. <br /> Form 890C(May 9,2002) <br /> 2002 Vaporless Manufacturing,Inc.,Prescott Valley,AZ Dialysis North <br /> P.O.Box 95 <br /> Bella Vista,CA 96008 <br /> (530)275-6667 <br />