Laserfiche WebLink
SWRCB;January 2002 ' ..i Page a of a <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: X Tank Manufacturer D Industry Standard D Professional Engineer <br /> D Other(Specify) <br /> Test Method Used: D Pressure X Vacuum D Hydrostatic <br /> U Other(Specify) <br /> Test Equipment Used: Vacuum Gage Equipment Resolution: .5"Hg <br /> Took#I-87 Tank# Tank# Tank# <br /> Is Tank Exempt From Testing?' D Yes X No U Yes D No U Yes D No D Yes D No <br /> Tank Capacity: 20,000 Gallon <br /> Tank Material: Glassteel <br /> Tank Manufacturer: Tnrsco <br /> Product Stored: 87 <br /> Wait time between applying <br /> pressure/vacuum/water and 10 Min <br /> sh rtin test: <br /> Test Start Time: 9:45 <br /> Initial Reading(Rj): 10"Hg <br /> Test End Time: 10:45 <br /> Final Reading(RF): 10"Hg <br /> Test Duration: 1 Hour <br /> Change in Reading(RF-R,): On Hg <br /> Pass/Fail Threshold or Criteria: +/-0"Hg +/-0"Hg +/-0"Hg +/-0"Hg <br /> Test Reault: X Pass D Fail ❑ Paas D Fail 1 ❑ Pass D Fall D Pass D Fail <br /> Was sensor removed for testing? X Yes D No 0 NA D Yes D No DNA D Yes D No D NA D Yes D No D NA <br /> Was sensor properly replaced and X Yes 0 No DNA D Yes D No D NA D Yes D No D NA D Yes D No D NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommendedfoAow-up for faded tests) <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> ...�.;nn frsr.�.n;,f'nria nFaemdatinnc T:eP�z c..".;nn or;zvsvFii <br />