Laserfiche WebLink
Installation and Maintenance Manual <br /> CNI Manufacturing Phase I Vapor Recovery System Page 24 of 28 <br /> Figure E-2 <br /> Emco Wheaton Vapor Adapter <br /> EMCO" A0076- 124 <br /> WHEATON RETAIL Swivel Vapor Adapter <br /> INSTALLATION INSTRUCTIONS <br /> -------------- <br /> A0076-124 <br /> 'rt Swivel Vapor <br /> Adapter <br /> Base <br /> Set Screw o <br /> (Total of 2) +E--- Flat Gasket <br /> p1n 409628 <br /> a <br /> i <br /> i <br /> x <br /> 1. Using a 5132"Allen wrench,remove both set screw from the base of the <br /> swivel adapter. <br /> 2. The top edge of the top riser nipple must be filed flat and square,with <br /> threads free of all debris to insure a proper sealing surface between the <br /> riser nipple and the base of the swivel adapter. <br /> 3. Before installing the swivel adapter, verify that the flat gasket is properly in <br /> place. Manually tighten the swivel adapter on to the top riser nipple to <br /> avoid cross threading. Using the Emco Wheaton Retail A0081 Adapter <br /> Wrench, torque the swivel adapter to 35 ft-lbs- <br /> IMPORTANT: Do not use pipe thread sealant compound when <br /> installing the swivel adapter. <br /> 4. Apply lock-tite model#222MS on both set screws. Re-install and torque to <br /> 20 in-lbs. <br />