Laserfiche WebLink
FEB-20-2006 15:13 Service Station Systems 408 938 8888 P.07/07 <br /> '✓ <br /> ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR OVERFILL CONTAINMENT <br /> Site Name:SafeWay#1769 Test Compaq: Ser. Sta. Sys. License# 485184 <br /> Address:2802 Country Club Blvd. Address: 680 Quinn Ave. <br /> Stockton, CA 95204- San Jose CA 95112 <br /> Technician : SSS-MattM Date 1/24/06 <br /> Test Method Developed By: []Spill Bucket Manufacturer Qx Industry Standard []Professional Engineer ❑Other(Speciry) <br /> Test Method Used: ®Hydrostatic ❑Other(Spea/ly) <br /> Test Equipment Used:Measuring Tape Equipment Resolution:l/16 in. Example-1/8"increments <br /> spur Bos#01 Regu Spill Box#02PIus Spill Box#03Prem Spill Box# <br /> Fill Vapor Fill Vapor Fill Vapor Fill Vapor <br /> Bucket Capacity in gallons: 5 5 5 5 5 5 <br /> Bucket Depth: 15.0 in.; 15.0 in. 16.0 in. 16.0 in. 14.0 in. 15.5 in. in, in. <br /> Wait time between filling with <br /> water and starting test: 30 min. 30 min. 30 min. min. <br /> Test Start Time: 926 am 9:26 am 9:26 am <br /> Initial Reading (RI): 5.25 in.! 6.25 in, 7.50 in. 7.75 in. 5.50 in.l 5-50 in. inj in. <br /> Test End Time: 1 10:26 a 10:26 a 10:26 a <br /> Final Reading (RF): 5.25 in-1 6.25 in. 7.50 in. 7.75 in. 5.50 in-1 5.50 in. in. in. <br /> Test Duration: 1.00hr. 1,00hr. 1.00hr. hr. <br /> Change in Reading (RI- RF): 0.00 i 0.00 0.00 I 0.00 0.00 i 0.00 <br /> Pass/Fail Threshold or Criteria: Zero Loss Zero Loss Zero Loss zero Loss <br /> TBSt;J�esYlt „r Pass Pass Pass I Paw I Pass I Pass <br /> momSpill Box# Spill Box# Spill Box# Spill Box# <br /> Fill Vapor Fill Vapor Fill Vapor Fill ! Vapor <br /> Bucket Capacity in gallons: <br /> Bucket Depth: in. in. in.i in. in. in. in.j <br /> Wait time between filling With <br /> water and stalling test: mill. min. min. min. <br /> Test Start Time: <br /> Initial Reading (RI): in. in. in.i in. in. in. in.l <br /> Test End Time: <br /> Final Reading (RF): in. in. in.l in, ind in. ial <br /> Test Duration: hr. hr, hr. hr. <br /> Change in Reading (Rt-RF): <br /> Pass/Fail Threshold or Criteria: Zero Loss Zero Loss Zero Loss Zero Loss <br /> Comments- <br /> TOTAL P.07 <br />