UNDER DISPAER CONTAINMENT (POC) TESTING <br /> Test Method By: o Manufacturer • Industry Standard o Professional Engr o Other(see below) <br /> Test Method Uses: O Pressure vacuum • Hydrostatic o Other(see below) <br /> Measuring Equipment Used: INCON TS-STS (Electronic Sump Test System) <br /> Description Disp#1/2 Disp#3/4 Disp#5/6 Disp#7/8 <br /> UDC manufacturer Bravo Bravo Bravo Bravo _ <br /> UDC material Steel Steel Steel Steel <br /> UDC depth (inches) 9 9 _ 9 9 <br /> Height from UDC bottom to highest Bottom Bottom Bottom Bottom <br /> piping penetration <br /> Height from UDC bottom to lowest Bottom Bottom Bottom Bottom <br /> electrical penetration _ <br /> Condition of UDC prior to testing Dry Dry _ Dry _ Dry <br /> Portion of UDC tested Entire Entire Entire Entire <br /> Type of shut-down present Float Float _ Float __ Float <br /> Was sensor removed for testing? N/A N/A N/A _ N/A <br /> Was sensor properly replaced after testing? N/A N/A N/A N/A <br /> Depth of water level from UDC bottom (in.) 6 6 _ 6 6 <br /> Wait time for water level to stabilize (hr:min) 0:05 0:10 0:10 0:05 <br /> Test start time 1:30 PM 1:30 PM 12:22 PM 12:22 PM _ <br /> Initial Probe Reading 0.1924 0.7132 0.4227 0.9769 <br /> Test end time 1:45 PM 1:45 PM 12:37 PM 12:37 PM <br /> Final Probe Reading 0.1924 0.7124 0.4232 0.9763 <br /> Test duration (hr:min) 0:15 0:15 0:15 0:15 <br /> Change in water level (±0.0000 inches) 0.0000 -0.0008 0.0005 -0.0006 <br /> Pass/Fail threshold (±0.0020 inches/;Hr.) 0.0020 0.0020 _ _ 0.0020 0.0020 <br /> TEST RESULT PASS PASS PASS PASS <br /> Comments: <br /> 2004 Walton Engineering,Inc. <br />