Laserfiche WebLink
Alltech <br /> 17759 Buttercup Circle, Sonora, CA 95370 <br /> Phone: 209-532-7320; Fax: 209-533-2650 <br /> California Tank Tester: 90-1068 <br /> alltech@mlode.com <br /> PRECISION TEST DATA SHEET for PIPING <br /> Facility: Lathrop Gas & Food Date: 10-Feb-03 <br /> Address: 14800 W. Frontage Rd., Manteca CA 95336 <br /> Contact: Elite IV Contractors Phone:461-6338 <br /> L.I.A.: San Joaquin County L.I.A. Phone: <br /> Hasstech Accu-Rite Pressurized Pi in Tester <br /> Product 1 Re 2 Dsl 3 Prem 4 <br /> Turbine isolation method * BV BV BV <br /> Dispenser isolation method Im Imp. Imp. <br /> Test pressure, PSI 50 50 50 <br /> Initial under level 0.0500 0.0500 0.0500 <br /> Final cylinder level 0.0500 0.0475 0.0500 <br /> Time Started 1330 1400 1430 <br /> Time Completed 1330 1400 1430 <br /> Total test time, minutes 30 30 30 <br /> Result: Volume change in GPH 0.00 0.005 0.00 <br /> Conclusion: **Pass Fail I Pass Pass Pass <br /> Leak Detector Test: I Pass Pass I Pass <br /> * S.B. _ "Silver bullet" isolation plug; LD Plug = Plugged leak detector. <br /> ** Pass/Fail threshold is 0.0100 GPH per Manufacturer's protocol. <br /> Remarks: Diesel still had a little air in the lines. <br /> I declare under penalty of perjury that I am a licensed tank tester in the State of California <br /> and that the information contained in this report is true and correct to the best of my <br /> knowledge. <br /> Date ��D 69 r�"`� Mike Dotten, License # 90-1068 <br />