Laserfiche WebLink
MOORE PETROLEUM <br /> •.LATHROP RD. /HWY 99 <br /> MANTECA CA. <br /> TANK TESTER VER 2.01 , <br /> FEEL TYPE: UNLEADED <br /> CAPACITY TANK 1: 9732 GALLONS <br /> TEMPERATURE COEFFICIENT: 688- ppm/deg F <br /> TEST CRITERIA: +0.050 GPH TO -0.050 GPH <br /> 01/06/89 TEST TIME FROM 11:55 TO 12:28 <br /> DATA ANALYSIS INDICATES: <br /> A GROSS VOLUME CHANGE OF: -0. 147 GALLONS <br /> A VOLUME CHANGE DUE TO TEMPERATURE OF: -0. 149 GALLONS <br /> A LIQUID VOLUME RATE OF CHANGE OF: +0.008 GPH <br /> WITH A 99 % CONFIDENCE INTERVAL OF: +/-0.013 GPH <br /> (+0,021 TO -0.005 GPH) <br /> TESTER. <br /> CUSTOMER. . . . . . . . . . . . . . <br />