Laserfiche WebLink
Monitoring System Certification <br /> A Results of Testing/Servicing <br /> Software Version Installed: 325.02 <br /> Complete the following checklist: <br /> x Yes ❑ No* Is the audible alarm operational? <br /> x Yes ❑ No* Is the visual alarm operational? <br /> x Yes ❑ No* Were all sensors visually inspected, functionally tested,and confirmed operational? <br /> ❑ Yes x No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will <br /> not interfere with their proper operation? <br /> ❑ Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g., modem) <br /> x N/A operational? <br /> ❑ Yes x No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment <br /> ❑ N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate <br /> positive shut-down? (Check all that apply) x Sump/Trench Sensors; ❑Dispenser Containment Sensors. <br /> Did you confirm positive shut-down due to leaks and sensor failure/disconnection? x Yes; ❑No. <br /> x Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e., no <br /> ❑ N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank <br /> fill point(s)and operating properly? If so,at what percent of tank capacity does the alarm trigger? 90% <br /> ❑ Yes* x No Was any monitoring equipment replaced? If yes, identify specific sensors,probes,or other equipment replaced <br /> and list the manufacturer name and model for all replacement parts in Section E,below. <br /> x Yes* ❑ No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) <br /> ❑Product; ❑ Water. If yes,describe causes in Section E,below. <br /> x Yes ❑ No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable <br /> x Yes ❑ No* Is all monitoring equipment operational per manufacturer's specifications? <br /> * In Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. Comments: 97 FIL L SirP S NSOR Wil I NOT TQ[ICH ROTTOM OE R1IMP '/ " SPACF S FNSOR WILI NOT <br /> FIT Wil I NEED TO INSTALL MICRO SENSOR <br /> gi o N Wil I NOT CLL IT DOWN GILD CCI Ay\NII 1 NEED TO BE REFI ACED <br /> I TN-036—2/4 www.unidocs.org Rev.01/26/06 <br />