Laserfiche WebLink
INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br /> .Tanknofogy <br /> 8501 N MOPAC EXPRESSWAY,SUITE 400 WORK ORDER NUMBER: 2283724 <br /> TEST DATE: 10/10/11 AUSTIN,TEXAS 78759(512)451-6334 <br /> CLIENT: 7-ELEVEN, INC. SITE: 7-ELEVEN #17334 MKT 2368 <br /> TANK/1NF0 - <br /> Tank ID: #2 2 Tank manifolded: No Bottom to top fill in inches: 128.0 <br /> Product: PREMIUM Vent manifolded: RES Bottom to grade in inches: 138.0 <br /> Capacity in gallons: 10,028 Vapor recovery manifolded: YES Fill pipe length in inches: 32.0 <br /> Diameter in inches: 96.00 Overfill protection: YES Fill pipe diameter in inches: 4.0 <br /> Length in inches: 324 Overspill protection: YES Stage I vapor recovery: DUAL <br /> Material: DW STEEL Installed: ATG Stage II vapor recovery: ASSIST <br /> i - CP installed on: / / <br /> COMMENTS <br /> TANK TEST RESULTS Test Method:NONE ..:.:. 'LEAK DETECTOR TEST RESULTS,-,' Test method.,%' <br /> PSI at tank bottom: New/passed Failed/replaced New/passed Failed/replaced <br /> Fluid level in inches: L.D.#1 L.D.#1 L.D.#2 L.D.#2 <br /> UFT/OFT: Make: VAPORLESS <br /> Fluid volume in gallons: Model: LD2000 <br /> Tank water level in inches: S/N: 04011558 <br /> Test time: NOT Open time in sec: 4.00 <br /> Number Of thermisters: TESTED Holding psi: 27 NOT <br /> Specific gravity: Resiliency cc: 100 TESTED <br /> Water table depth in inches: Test leak rate ml/m: 189.0 <br /> Determined by(method): Metering psi: 20 <br /> Leak rate in gph: Calib. leak in gph: 3.00 <br /> Result: Results: PASS <br /> COMMENTS COMMENTS <br /> s v UST <br /> Test time: <br /> Ullage volume: Material: DN FLEX <br /> Ullage pressure: Diameter(in): 2.0 <br /> Results: Length (ft): 80.0 <br /> Test psi: <br /> DATA FOR UTS-4T ONLY: Bleedback cc: <br /> Time of test 1: Test time(min): <br /> Temperature: NOT Start time: NOT NOT NOT NOT <br /> Flow rate(cfh): TESTED End time: TESTED TESTED TESTED TESTED <br /> Time of test 2: Final gph: <br /> Temperature: Result: <br /> Flow rate(cfh): Pump type: PRESSURE <br /> Time of test 3: Pump make: FE PETRO <br /> Temperature: <br /> Flow rate(cfh): Impact Valves Operational: YES <br /> COMMENTS COMMENTS <br /> Printed 10/21/2011 07:40 MTUTTLE <br />