Laserfiche WebLink
OCT 05 2004 7:18 AM FR r ' 1 562 597 8459 '-'l 12094683433 P.05 <br />09/27/2004 10:26 156286,x,10 ATUM ENVIRUNME1�wL B tALE hd <br />Sump, dispenser, pan and/or spill containment bucket (and fill sump if required): <br />1. Test liquid in sumps and dispenser containment must be 2 inches above all penetrations <br />(product, vent, vapor, siphon and electrical). <br />2. Sumps must be within +/-.002 inches to pass test after (2)15 -minutes test periods. <br />3. Introduce water into containment area until the desired height is reached. (Highest <br />penetration). <br />4. Let stabilize far 30 minutes. <br />5. Secure probes and equipment as needed.. <br />6- Start test using Incon Ts -St, <br />7. Test for 15 minutes (watching for a level change that could be greater than .002 inches). <br />8. Test again for another 15 minutes <br />9. Test will be deemed "pass" or "fail". Accuracy of +/- .002. <br />Water will be pumped out into drums. The drums will be labeled and disposed of using proper <br />EPA Department of Tonics regulations. <br />Written test results will be submitted within 30 days. (Report will include local agency requirement, but <br />not less that State requirement - see attached). <br />Please note: local regulations will be attached and used in lieu of this submittal if deemed necessary. <br />