Laserfiche WebLink
FFS ML ) Pipeline Leak Detector <br /> Ken Wilcox Associates, Inc. has demonstrated that , based on the test data provided, the <br /> STP-MLD-D system will successfully perform on such pipeline systems containing Diesel <br /> fuel. <br /> If the EPA protocol is used to calculate the performance parameters, the STP-MLD-D system <br /> can be used on rigid pipelines up to 341 gal (twice the volume of that tested), which is <br /> equivalent to 800 ft. of 3-in fiberglass pipeline with a Po of 95%or greater and a P,:,,of 5% or <br /> less. <br /> Although the STP MLD shown to perform adequately on smaller lines, caution should be <br /> used in testing larger lines containing Ultrazol. A simulated leak test to demonstrate that <br /> a 3 gph leak can be detected is advised. <br /> 3 <br />