Monitoring System Certification • • ���� <br /> D. Results of Testing/Servicing <br /> Software Version Installed: 326.01 <br /> Complete the following checklist: <br /> NX Yes ❑ No* Is the audible alarm operational? <br /> XN Yes ❑ No* I Is the visual alarm operational? <br /> ❑ Yes ❑X No* I Were all sensors visually inspected,functionally tested, and confirmed operational? <br /> XN Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will <br /> not interfere with their proper operation? <br /> ❑ Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) <br /> N N/A operational? <br /> I]Yes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment <br /> ❑ N/A monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate <br /> positive shut-down? (Check all that apply) NX Sump/Trench Sensors; N Dispenser Containment Sensors. <br /> Did you confirm positive shut-down due to leaks and sensor failure/disconnection? NX Yes; ❑No. <br /> NXYes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no <br /> ❑ N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank <br /> fill point(s)and operating properly'? If so,at what percent of tank capacity does the alarm trigger? 90% <br /> ❑ Yes* M No Was any monitoring equipment replaced? If yes, identify specific sensors,probes,or other equipment replaced <br /> and list the manufacturer name and model for all replacement parts in Section E,below. <br /> NX Yes* ❑ No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) <br /> NX Product; NX Water. If yes,describe causes in Section E,below. <br /> NX Yes ❑ No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable <br /> 11Yes NX No* 1 <br /> Is all monitoring equipment operational per manufacturer's specifications? <br /> *In Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. Comments: <br /> L2 — Diesel 1 STP Sump Brine Sensor — 420 <br /> L4 - Diesel 2 STP Sump Brine Sensor - 420 <br /> L6 - Diesel 1 Fill Sump Brine Sensor - 420 <br /> L8 - Diesel 2 Fill Sump Brine Sensor - 420 <br /> L11 - Vent Sump Sensor - 208 <br /> L12 - Vent Sump Brine Sensor - 420 <br /> L14 - Dispenser 13 Brine Sensor - 420 <br /> L16 - Dispenser 14 Brine Sensor - 420 <br /> L18 - Dispenser 15 Brine Sensor - 420 <br /> L20 - Dispenser 16 Brine Sensor - 420 <br /> L22 - Dispenser 17 Brine Sensor - 420 <br /> L24 - Dispenser 18 Brine Sensor - 420 <br /> L7 - Diesel 2 Fill Sump Sensor 208 does not alarm - need to replace <br /> DN-036-2/4 Page 2 of 4 Rev.06/04/01 <br /> w .unidocs.org <br />