Laserfiche WebLink
Vaporless Manufacturing, Inc. <br /> Quality Petroleum Equipment <br /> Solutions for Over 20 Years <br /> LDT- 890 Test Form &VMI Warranty Checklist <br /> Octoher 1 ,2006 <br /> Test Information: <br /> Date: 6/20/2012 Test Company: EPIC Compliance Systems Inc. <br /> Telephone: 707-326-0369 Contact: Hardeep Gill <br /> Site I.D: Fast Lane-Lathrop (Auto) Address: 116 East Roth Road <br /> City: Lathrop State: CA Zip: 95330 <br /> Type of Test Equipment: LDT-890 <br /> Submersible Pump Identification: <br /> MFG: FE Petro Model No: STPMR200-VL3-51 Serial No: 06110285 <br /> Leak Detector Identification: <br /> MFG: VMI Model No: 99LD2000 Serial No: 08121042 <br /> Replacement Leak Detector Identification: <br /> MFG: Model No: Serial No: <br /> Line Conditions <br /> 1. Type of Pipe: F.G. 2. Diameter of Pipe: 2" 3. Length of Pipe: 200' <br /> 4. Burial Depth of Leak Detector: 12" 5. Kind of Fuel: 91 6. Date of Last Line Test: — <br /> Test Conditions <br /> 1. Operating Pump Pressure: 29 2. Gallon per hour test rate: 3 @ 10 psi <br /> 3. Static Line Pressure (Pump Off: 29 4. Bleedback Test(Pump Off): 160 ml. <br /> 5. Step-through time to full flow 4 seconds (0 psi. to full pump pressure, no leak) <br /> 6. Leak detector stays in Leak Search Position with a 3 GPH leak -Yes: ✓ PASS No: FAIL <br /> 7. Was the leak detector adjusted -Yes: No: ✓ <br /> Symptoms <br /> 1. Won't find 3 GPH leak: 2. Stays in Slow Flow: <br /> 3. Other: <br /> *********** If This Unit Is Returned Under Warranty Please Complete The Following *********** <br /> Vaporless RGA#: Return By (Company): <br /> Telephone: Contact: <br /> Customer Control #: Address: <br /> City: State: Zip: <br /> (See Website -www.vaporiess.com -Technical Bulletin 032805) <br />