Laserfiche WebLink
Page 1 of 1 <br /> Willy Ng [EH] <br /> From: Willy Ng [EHj <br /> Sent: Monday, April 17, 2006 9:30 AM <br /> To: 'jsouthward@rhldesign.com' <br /> Subject: 316 Roth Rd <br /> Jim, <br /> There are a few items that need to be clarified before the plans can be approved <br /> 1. RE: two 20K gallon diesel tanks. Per Paul Kulicamp ((608)838-5665), Technical Services Engineer at FE <br /> Petro: <br /> a. Both turbines need to have a STP-MLD installed, OR <br /> b. One electronic leak detector and one check valve installed, OR <br /> c. Have lines manifolded in master sump. <br /> 2. Plans need to show a drawing of the vapor recovery line entering the sump and tank. <br /> 3. Plans need to show the vacuum source for the vent and vapor recovery lines. <br /> 4. Provide specs for backfill material per manufacturer installation instructions. <br /> 5. Provide an approval letter from the City of Lathrop for the underground sewage storage tank. <br /> Please call if you have any other questions. <br /> Thanks, <br /> Willy Ng, Sr. R.E.H.S <br /> San Joaquin County <br /> Environmental Health Department <br /> (209)468-3448 <br /> (209)468-3433 fax <br /> 4/17/2006 <br />