Laserfiche WebLink
0 ED <br /> SWRC ,January 2002 JUL 07 20i�age—of <br /> 11 4. TANK ANNULAR TESTING ENVIRONMENTAL HEALTH <br /> Test M "' od Developed By: X Tank Manufacturer ❑Industry Standard meer <br /> ❑Other(Spec) <br /> Test M hod Used: ❑Pressure X Vacuum ❑Hydrostatic <br /> ❑Other(Specify) <br /> Test Eq' ipment Used: Gast Vacuum Pump/Vacuum Gauge in Hg. Equipment Resolution:- %z"x 30"Hg. <br /> Tank# 1 Tank# Tank# Tank# <br /> MIsTank Testing?' No <br /> Tank Capacity: 12K <br /> Tank Material: Fiberglass <br /> Tank Manufacturer: XERXES <br /> Product Stored: Diesel <br /> Wait tir ie between applying 10 Minutes <br /> vacuum and starting test: <br /> Test SU rt Time: 12:30 <br /> Initial Reading(R,): -10 Hg. <br /> Test E4 Time: 1:30 <br /> Final R'ading(RF): -10 Hg. <br /> Test Duration: 1 Hour <br /> Change in Reading(Rr-R,): 0 Hg. <br /> Pass/Fail Threshold or Criteria: ➢ -2 Hg. <br /> Test Result: Pass <br /> Was sensor removed for testing? Yes <br /> Was sensor properly replaced and Yes <br /> verified'.functional after testing? <br /> Com cats—(include information on repairs made prior to testing, and recommended allow-u or ailed tests <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) <br />