Laserfiche WebLink
OIL EQUIPMENT SERVICE STATE LICENSE No.323417 <br /> CLASSIFICATION: A- AZ.,C61D40 <br /> Division of Keith A. Tallia, Inc, STATE ENVIRONMENTAL ASSESSOR No. 01781 <br /> Telephone: 209)754-1808 <br /> Fax: 209)754-5726 <br /> LEAK DETECTOR TEST RECORD Post Office Box 950 <br /> 75C Industrial Way <br /> SAN ANDREAS,CALIFORNIA 95249 <br /> Customer Date <br /> Bob Cat Central 10/2.4 00_ <br /> Location <br /> 1113 Shaw Rd. , Stockton, CA 95205 _ <br /> Technician Product <br /> James P. Hesketh Regular Gasoline <br /> —e <br /> Submersible Pump Identification <br /> Manufacturer Model No. Serial Number <br /> Tokheim <br /> Leak Detector Identification <br /> Manufacturer Description Other Style Leak De erWr <br /> Campo/Miller Diaphragm-type_ Electronic <br /> Piston-type <br /> Tamper-proof seal installed? Yes No X <br /> Leak Detector in Submersible Pump <br /> Test at Dispenser <br /> I. Operating Pump Pressure 22. 5 psi (para. 15) <br /> 2. Gallons per hour rate 3 (para.22) <br /> 3. Line pressure with pump shut off 20 psi (para.23) <br /> 4. Bleedback Test with pump off 10 ml (para.26) <br /> 5. Step-through time to full flow N/A .-_seconds(para. 30) <br /> 6. Leak detector stays in leak search position. (para.42) Yes N/A <br /> No N A <br /> LEAK DETECTOR TEST *Complete thermal expansion test <br /> Not.: Pass L ikdetectorfitstestpnxO of before failing leak detector <br /> Fail=Luak detector fails test protmoi <br /> Pass X Turbine Shut Down <br /> Fail.._ ._-_ _.. <br /> 10/24/00 <br /> T 0cs <br /> f n DateP .Hesketh <br />