Laserfiche WebLink
• <br /> OIL EQUIPMENT SERVICE STATE LICENSE No.323417 <br /> CLASSIFICATION: A- Z.,C61D40 <br /> Division of Keith A. Tallia, Inc. STATE ENVIRONMENTAL ASSESSOR No.01761 <br /> Telephone: (209)754-1000 <br /> Fax: (209)754-5726 <br /> Post Office Box 950 <br /> 750 Industrial Way <br /> SAN ANDREAS,CALIFORNIA 95249 <br /> Page 1 of 2 <br /> March 23, 1999 <br /> San Joaquin County <br /> Public Health Services <br /> Environmental Health Div. <br /> Hazardous Material Section <br /> P.O. Box 388 <br /> Stockton, CA 95201 -0388 <br /> ATTN: UST Coordinator <br /> SUBJECT: Bob Cat Central <br /> 1113 Shaw Rd. <br /> Stockton, CA 95215 <br /> Dear Coordinator, <br /> This is to advise that on March 16, 1999 our techni ian <br /> performed the following tests with the following results on <br /> the existing underground motor fuel and waste oil storage tnks <br /> at subject site: <br /> 1 . Tested the cathodic protection on the Slip-3 gasoline <br /> and diesel tanks with results of: <br /> Gasoline 1216 milli volts <br /> Diesel 1080 milli volts. <br /> Both well within allowable perimeters. <br /> 2. Tested annular space sensors on all 3 tanks. The <br /> sensors in the diesel and waste oil tanks were in good <br /> condition and functioning properly. The sensor in <br /> the gasoline tank was defective and inoperative. A <br /> new sensor was installed on March 22, 1999 . Tested <br /> O.K. <br /> 3. Piping sump sensors on the gasoline and diesel tanks <br /> were tested. Both in good condition and functioning <br /> properly. <br />