Laserfiche WebLink
IT TS Integrity Tank Testing Systems, Inc. <br /> TEST DATA AND <br /> TEST RESULTS <br /> December 4 , 1987 <br /> .BOBCAT CENTRAL <br /> 1113 Shaw Road <br /> Stockton , California 95295 <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Attached are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency . <br /> A tank system is considered tight , according to the current: <br /> rules , if the gain is less than . 02 or the loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you Should consider taking some remedial action. <br /> TANK #/ TANK PRODUCT TEST WITHIN TIGII'r <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> North side 550 Diesel Fuel +. 01207 Yes <br /> of shop <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> 1 <br /> Frank Kes r <br /> Certified eter <br /> 800 262 TEST 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />