My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2015 - 2018
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
T
>
THORNTON
>
15250
>
2300 - Underground Storage Tank Program
>
PR0537919
>
COMPLIANCE INFO_2015 - 2018
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
11/29/2023 2:20:42 PM
Creation date
11/8/2018 9:54:20 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2015 - 2018
RECORD_ID
PR0537919
PE
2351
FACILITY_ID
FA0021886
FACILITY_NAME
Love's Travel Stop #538
STREET_NUMBER
15250
Direction
N
STREET_NAME
THORNTON
STREET_TYPE
RD
City
Lodi
Zip
95242
CURRENT_STATUS
01
SITE_LOCATION
15250 N THORNTON RD
P_LOCATION
99
P_DISTRICT
004
QC Status
Approved
Supplemental fields
FilePath
\MIGRATIONS3\T\THORNTON\15250\PR0537919\COMPLIANCE INFO 2015 - PRESENT.PDF
QuestysFileName
COMPLIANCE INFO 2015 - PRESENT
QuestysRecordDate
12/7/2017 11:45:50 PM
QuestysRecordID
3743012
QuestysRecordType
12
QuestysStateID
1
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
201
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
Environmental Health Department <br />Underground Storage Tank Program Inspection Report <br />Date: <br />June 01, 2018 <br /> Facility Address: <br /> 15250 N THORNTON RD, LODI <br /> Facility Name: <br /> LOVES TRAVEL STOP #538 <br />UST System Observations <br /> 319 □ V □ R □ COSNo spill bucket, failed to contain five gallons, or failed to provide a means to keep it emptyCCR 2635(b) <br /> 320 □ V □ R □ COSOverfill prevention system not present or failed to meet overfill requirementsCCR 2635(b)(2) <br /> 321 □ V □ R □ COSOverfill prevention was overriddenCCR 2635(b)(2) <br /> 322 □ V □ R □ COSUnburied below grade emergency generator system failed to meet exemption statusHSC 25281.6(a) <br /> 323 □ V □ R □ COSUnburied below grade UST system failed to meet exemption statusHSC 25283.5(a) <br /> 324 □ V □ R □ COSTampered with red tagCCR 2717.1(g) <br /> 325 □ V □ R □ COSDeposited petroleum into a red tagged USTCCR 2717.1(f) <br /> 326 □ V □ R □ COSTampered with or disabled leak detection devices or alarmsHSC 25299(a)(9) <br /> 327 □ V □ R □ COSUST system not compatible with the substance storedCCR 2631.1 <br /> 328 □ V □ R □ COSFailed to comply with temporary closure requirementsHSC 25298 <br /> 329 □ V □ R □ COSFailed to comply with all permanent closure requirementsHSC 25298 <br /> 330 □ V □ R □ COSFailure to meet all requirements in lieu of a line leak detector for emergency generator tank systemCCR 2636(f)(6) <br /> 331 □ V □ R □ COSSecondarily contained piping not maintained to allow liquid to drain into sumpCCR 2630(d) <br /> 332 □ V □ R □ COSPrimary and/or secondary containment not constructed in accordance with the established standardsCCR 2631(b), 2631(d) <br />Single-Walled Non-Pressurized Piping <br /> 401 □ V □ R □ COSSuction piping not properly sloped or incorrectly located check valveCCR 2636(a)(3) <br /> 402 □ V □ R □ COSDaily monitoring of suction pipe (pre-Jan 1984) not performedCCR 2643(d) <br /> 403 □ V □ R □ COSTriennial 0.1 gph line test for conventional suction piping not performed (pre-January 1984)CCR 2643(d) <br /> 404 □ V □ R □ COSBiennial 0.1 gph test for gravity piping not performed (pre-January 1984)CCR 2643(e) <br />Other Violations <br /> 2010 □ V □ R □ COSUnlisted General violation See below <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />RemarksItem # <br />Overall Inspection Comments: <br />Onsite for a billable reinspection (billed at EHD current hourly rate) to verify vacuum communication in the <br />dispensers, and vent box for each product line since it was not tested during the annual monitoring system <br />certification on 4/12/18. Could not verify vacuum communication in the vent box, or any of the 87-product lines in <br />each dispenser. The vent box had no test ports installed for testing. When the 87-product lines were tested in <br />each dispenser, there was no indication of communication. <br />Testing of the vacuum communication in the vent sumps, and on the 87-product lines in each dispenser will <br />need to be verified to complete the annual monitoring system certification and will be billable at EHD hourly rate. <br />Please refer to amended inspection report dated 5/9/18 for a complete list of outstanding violations. <br />Please be aware that as of January 1, 2014, facility operators are required to upload the following UST program <br />Page 3 of 4 <br />FA0021886 PR0537919 SC333 06/01/2018 <br />EHD 23-01 Rev. 10/31/2017 Underground Storage Tank Program OIR <br />1868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjcehd.com
The URL can be used to link to this page
Your browser does not support the video tag.