Triangle Environmental, Inc. <br /> SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Phillips Facility <br /> Tank #: 2 Test Date: 6/ 6/02 <br /> Product: Unleaded Premium Work#: 12901008 <br /> Test Method: Test Method: R.J. FTA <br /> Capacity: 9816 Manufacturer: Red Jacket <br /> Diameter(in): L/D Model: FX <br /> Product Level(in): L/D Serial#: 9492 <br /> Liquid Volume(Gals): Line Drain Back(ml): 62 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 24 <br /> Coef. of Expansion: Metering Pressure(psi): 9 <br /> Water On Tank(in): L/D Test Rate(gph): 2.9 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? No <br /> Head Pressure(psi): <br /> Test Start Time: <br /> Test End Time: Test Method: TEI LT-3 <br /> Test Rate(gph): Pump Brand: Red Jacket <br /> Test Result: N/A System Type: Pressure <br /> �- Line Pressure(psi): 50 <br /> Of MENIS1 Line Start Time: 11:00:00 AM <br /> Test Method: ULLAGE Line End Time: 11:15:00 AM <br /> UllageVolume(gals.): Line Start Level: 310 <br /> Ullage Test Time: Line End Level: 310 <br /> Ullage Vacuum(psi): I Line Test Rate(gph): X000, <br /> Ullage Result: N/A Line Test Result: PASS <br /> 1 <br /> , x <br /> 2 <br />