Laserfiche WebLink
i <br />E <br />KCJ Engineering Inc. <br />25431 Cabot, Suite 109 Client: California Hazardous <br />Laguna Hills, CA. 92653-55: Project: F-ENC07 Vent Line Enclosure <br />Tel (949) 380-8186 Date: 1/13/2009 <br />Fax (949) 588-1664 <br />• Tank Designed by Others <br />. See California Hazardous <br />j • Use 130 MPH Basic Wind Speed, Exposure C <br />All Steel to be A36 or Equal, UNO <br />. Use 2006 International Building Code (2007 California Building Code) <br />General Enclosure Dimensions <br />H <br />Total Enclosure Height <br />70 in. <br />W <br />Total Enclosure Width <br />16 in. <br />L <br />Total Enclosure Length <br />21.5 in. <br />H' <br />Height to Vertical Centroid <br />35 in. <br />Loading- <br />General <br />oading <br />General Enclosure Weight Head Loadl <br />16 Gauge design thickenss = 0.0566" <br />Steel Density = 450 PCF <br />Weight 16 Gauge sheet = 450 PCF x 0.0566/1 2.13 PSF <br />Total Weight = 2.13 PSF x 6'x 2'x 4 sides 103 lb <br />Seismic <br />Assume Cs = 1 (Worst Case) <br />Fp 103 Ib <br />Steel Enclosure Page 1 <br />