Laserfiche WebLink
CERTIFICATE OF UNDERGROUND STORAGE TANK SYSTEM TESTING <br /> or Tanlmo/ogy <br /> 8900 SHOAL CREEK, BUILDING 200 <br /> AUSTIN,TEXAS 78757 <br /> (512)451-6334 <br /> FAX (512)459-1459 <br /> TEST RESULT SITE SUMMARY REPORT <br /> PURPOSE: COMPLIANCE <br /> TESTDATE: 09/26/01 CUSTOMER PO. WORK ORDER NUMBER: 2218655 <br /> CLIENT: CHEVRON, U.S.A. SITE: CHEVRON #98264 <br /> P.O. BOX 6004 3775 TRACY BLVD <br /> ROOM L1338 @ I-205 <br /> SAN RAMON, CA 94583 TRACY, CA 95376 <br /> CHARLES BITTLE MGR — PAT <br /> (800) 537-2389 (209)836-9422 <br /> The following test(s)were conducted at the site above in accordance with all applicable portions of Federal,NFPA and local regulations <br /> Line and Leak Detector Tests <br /> VOLUME CHANGE LINE RESULT LEAK LEAK IMPACT <br /> TANK PRODUCT (9ph) (P—pass,F=tail DETECTOR DETECTOR VALVES <br /> NUMBER 1=inconclusive) PRESENT RESULT OPERA- <br /> A B C D A 8 C D #1 #2 #1 42 TIONAL <br /> 92 1 SUPREME Y P <br /> 89 2 PLUS Y P <br /> 87 3 REG UNLEAD Y P <br /> Tanknology appreciates the opportunity to serve you,and looks forward to working with you in the future.Please call any time,day or <br /> night,when you need us. <br /> Tanknology representative: Services conducted by: <br /> MARK SHAW MATT HEMMINGSEN <br /> Reviewed: Technician Certification Number: <br /> Printed 09/28/2001 08:55 CCHAPA <br />