Laserfiche WebLink
303.The south turbine sump sensor was located on the west side of the sump and not located to detect <br /> a leak at the earliest opportunity. Monitoring equipment shall be maintained to be able to detect a leak <br /> at the earliest possible opportunity. Immediately relocate this sensor to the lowest point of the east side <br /> of the south turbine sump which is where the product piping penetrates the sump wall. Do this so that if <br /> any fuel leaks into the product secondary piping,then the south turbine sump sensor would be able to <br /> detect the leak at the earliest opportunity. If the sensor must be rewired to reach the lowest point of <br /> the east side of the south turbine sump, contact a properly licensed, trained, and certified contractor to <br /> perform the repair under permit and inspection of the EHD. Complete and submit a copy of the Return <br /> to Compliance Certification form with a statement of how each violation was corrected, including <br /> supporting documentation, by May 9, 2014. <br /> • <br /> Sensor wire is too short to moue to the east side of the turbine sump. Permit will be required and sensor <br /> relocated. SWC is preparing proposal for work to be completed and will insure application is submitted <br /> to agency before May 9, 2014. <br /> If you have any questions, please do not hesitate to contact me directly at 888-588-8737 x 7014. <br /> Sincerely, <br /> e <br /> President <br /> attachments (2) <br /> RECEIVED <br /> APR 2 22014 <br /> ENVIRONMENTAL HEALTH <br /> DEPARTMENT <br />