Laserfiche WebLink
%�-- 1� <br /> I. MONITORING: All monitoring equipment must be listed in the State Waster Resources Control Board <br /> Division of Clean Water Program Local Guidance Letter 113. <br /> CheCk Code <br /> Box Swdon <br /> X 23 CCR All secondary containment units (e.g. tank annular spaces, secondary piping, sumps, <br /> 2632 under-dispenser containment, etc.) monitored for leaks using approved electronic leak <br /> 2636(f) detections stems. <br /> All sensors must be located at the lowest possible point so that they may detect a leak <br /> at the earliest opportunity. <br /> Electronic monitoring sensors located at the following points: <br /> ° At the bottom of the interstitial space of each secondarily-contained tank, <br /> positioned as near as possible to the bottom of the tank. <br /> Manufacturerveeder-Root Model 794380-303 <br /> ° In each collection sump, positioned as near as possible to the bottom of the <br /> collection sump. Additionally, in any sump acting as secondary containment for <br /> unused tank openings which connect to the primary space. <br /> X 23 CCR Manufacturer Veeder-Root Model 794380-208 <br /> 2632 <br /> 2630(d) <br /> • In dispenser pans which do not drain into secondary containment piping. <br /> (Note:A mechanical switch which triggers a shear valve may be substituted but <br /> this system will not qualify for the annual line tightness test exemption under 23 <br /> CCR 2636(g)), <br /> Manufacturer Veeder-Root Model 794380-208 <br /> Along secondarily-contained pipe runs which do not meet the 114 inch-per-foot <br /> slope requirement, positioned in the depressed or low-lying areas. <br /> Manufacturer Model <br /> 23 CCR Automatic line leak detectors installed to monitor underground pressurized piping. <br /> X 2636(f) <br /> HSC Manufacturer veeder-Root Model 848480-001 <br /> 25290.1 h <br /> 25290.2 <br /> Alarm panel provides both audible and visual alarms. It is located in a protected area <br /> and within sight and hearing distance of on-site personnel and hard-wired to a <br /> X 23 CCR <br /> j(2)(s) dedicated circuit. <br /> Manufacturer Veeder-Root Model 848290-022 <br /> J. OTHER COMPONENT INFORMATION: <br /> COMPONENT MANUFACTURER MODEL COMPOSITION <br /> Bravo B421X36-DB-XT Double Wall FRP <br /> SUMP B481X36-DB-XT <br /> UNDER-DISPENSER Bravo B8000F2LB-D-AB Double Wall FRP <br /> CONTAINMENT B8000F3LB-D-AB <br /> Smith Fibercast 012040-626-0 Double Wall FRP <br /> PENETRATIONS Bravo F-17-RR-D JFRP Robroy PVC- oated <br /> F-10-RR-D <br /> Revised 07/22/10 8 <br />