Laserfiche WebLink
REPORT oY 'SOILTEST' PRECISION TANKYfEST <br /> ---------------------------------------------- <br /> Customer : Teresi Trucking Date : 6/13/89 <br /> Address : 900 1/2 Victor Rd . City : Lodi <br /> Product Type : Diesel Tank Gallons : 10000 Tank 4 : 2 <br /> Test Results - 60 Minute Temperature Comparison <br /> Starting Time Fo , Temperature Check 08 : 05 - Completion Time 09 : 05 <br /> 1 . Weighted Temperature - Finish = 76 . 0164 <br /> ----------- <br /> 2 . Weighted Temperature - Start = 75 . 9954 <br /> ----------- <br /> 3- Weighted Temperature Change ( 2 from 1 ) . . . . . . . . . . . . . . = + . 021 <br /> 4 . Volume Change for Each Degree of Temperature Change = 4 . 652 <br /> 5- Volume Change Due To Temperature ( 3 x 4 ) . . . . . . . . . . . . = + . 098 <br /> Test Results - 60 Minute Volume Comparison <br /> Starting Time For Volume. . . . . Check 08 : 05 - Completion Time 09 : 05 <br /> 6_ Volume of Product Added (+) or Removed (-) During the test <br /> to Return " Test Level Indicator" to Starting Point = - . 073 <br /> 7. Leak Rate <br /> (gallons/hour) Add line 5 to line 6 . . . . . . . _ + . 025 <br /> This leak rate DOES NOT _e_xceed the standard of 0 . 050 gallons per hour <br /> described in the National Fire Protection Association , Bulletin <br /> N. F. P.A. 329 . <br /> S . Comments : <br /> ----------------------------------------------------------------------- <br /> All of the information used to determine the above results is true <br /> and accurate to the best of my knowledge and has been developed by <br /> using methods and procedures of the 'SOILTEST Tank 'Tegrity Tester' . <br /> Certified Technician CjaLA� ___Cert . #-12-: <br />