Laserfiche WebLink
REPORT of►wSOILTEST' PRECISION TANK IdST <br /> ---------------------------------------------- <br /> Customer : Teresi Trucking Date: 6/13/89 <br /> Address : 900 1/2 Victor Rd . City : Lodi <br /> Product Type : Waste Oil Tank Gallons : 1000 Tank 4 : 4 <br /> Test Results - 60 Minute Temperature Comparison <br /> Starting Time For Temperature Check 11 : 00 - Completion Time 12 : 00 <br /> 1 . Weighted Temperature - Finish = 70 . 3578 <br /> 2 . Weighted Temperature - Start . . . . . . . . . . . . . . . . . . . . . . . = 70 . 3838 <br /> 3 . Weighted Temperature Change (2 from 1 ) . . . . . . . . . . . . . . = - . 026 <br /> 4 . Volume Change for Each Degree of Temperature Change = . 4343 <br /> 5 . Volume Change Due To Temperature (3 x 4 ) . . . . . . . . . . . . = - . 011 <br /> Test Results - 60 Minute Volume Comparison <br /> Starting Time For Volume. . . . . Check 11 : 00 - Completion Time 12 : 0.0 <br /> 6 . Volume of Product Added (+) or Removed (-) During the test <br /> to Return " Test Level Indicator" to Starting Point = + . 008 <br /> 7 . Leak Rate (gallons/hour) Add line 5 to line 6 . . . . . . . _ - . 003 <br /> This leak rate DOES NOT exceed the standard of 0 . 050 gallons per hour <br /> described in the National-Ti re Protection Association , Bulletin <br /> N. F . P. A. , 329 . <br /> 8 . Comments : <br /> --------------------------------------------------------------------- <br /> ---------------------------------------------------------------------- <br /> All of the information used to determine the above results is true <br /> and accurate to the best of my knowledge and has been developed by <br /> using methods and procedures of the 'SOILTEST Tank ' Tegrity Tester'. <br /> Certified Technicia __ ______4 ���___Cart. <br />