Laserfiche WebLink
ITTS <br /> IV, <br /> Integrity Tank Testing SystemsInc.- a L U <br /> R f: CE IV EDENVIRONMENTAL. HEALTH <br /> jvl 0 199' PERMIT/SERVICES <br /> June 21, 1991 <br /> Mr. Jeff Post <br /> Post Tank <br /> 3633 Seaport Boulevard <br /> West Sacramento, California 95691 <br /> Site: Teresi Trucking <br /> Lodi, California <br /> Dear Mr, Post: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank. <br /> Enclosed are copies of the test worksheets, graphs, and/or <br /> computer summation for your submittal to the appropriate <br /> governmental agency. Individual computer generated readings <br /> will be forwarded as requested. <br /> A tank system may be considered tight, according to the <br /> current regulations if the the test results shown below do <br /> not exceed 0 . 05 gph. If the results are beyond this <br /> parameter, an unauthorized release may have occurred, and <br /> you should consider taking remedial action, <br /> TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> Northeast 10, 000 Diesel - .029.1/ Yes <br /> Southeast 12 , 000 Diesel - ,036/ Yes <br /> West 5, 000 Prem Gas +, 000 Yes <br /> East 1, 000 Waste Oil - , 0297 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> W. N. Savage <br /> Certified Tester <br /> 800 262-8378 166 1Yank West Circle Stockton, CA 95206 (209) 466-8036 <br />