Laserfiche WebLink
REPORT of "SOTLTEST" PRECTSTON' TANK TEST <br /> ---------------------------------------------- <br /> Customer : Teresi Trucking Date: 6/21/90 <br /> Address : 900 1/2 Vir.tor Rd ." City: I...odi <br /> Product Type : Diesel Tank Gallons : 10000 Tank # 3 . <br /> Test Results - 60 Minute Temeerature Comparison <br /> Starting Time For Temperature Check 10 : 30 - Completion Time 11 : 30 <br /> 1 - Weighted Ternper-a-, ire: -.. Finis;l-. . . . . . .. . . . .. . . . . . . .. .. . . . . 78 . 0696 _ <br /> 2 . Weighted Temperature_ - Start . . . . - . . . . . . . . . _ 78 . 0553 <br /> ------------ <br /> 3. Weighted Temperature Change ( 2 from 1 ) . . . . . . . . . . . . . . + . 014 <br /> 4 . Volume Change for Each Degree of Temperature Change = 4 . 067 <br /> ------------ <br /> 5- Volume Change Due To Temperature ( 3 x 4) . . . . . . . . . . . . _ + . 064 <br /> Test Results - 60 Minute Volume Comparison <br /> Starting Time For Volume . . . . . Check 10 : 80 - Completion Time 11 : 30 <br /> 6- Volume of Product Added (+) or Removed (-) During the test. <br /> to Return "Test I...evel Tndicator" to Starting Point- _ - . 038 . <br /> 7_ Leak Rate (gallons/hour) Add line 5 to line 6 . - . . . . . _ + . 026 <br /> This leak rate DOES NOT _e_xce_e.d the standard of 0 . 050 gallons per hour <br /> described in the National Fire Protection Association, Bulletin <br /> N- F . P.A. 329 . <br /> 8 . Comments : <br /> All of the information used to determine the ahnve results is true <br /> and accurate to the best of my knowledge and has been developed by <br /> using methods and procedures of the "SOTLTEST Tank 'Tegrity Tester' . <br /> Certified Techniciana,..,...- _t Lie. U-92-1120 <br /> --- -- ------ �Yt------ --- <br />