Laserfiche WebLink
7- 6-05; 9:41AM;Sacramento EMC ;918 9252816 # 7,' <br /> `i <br /> Customer Job Location Work Order 119676 <br /> Valley Pacific Cardlock Valley Pacific Cardlock Contact Pat Rooms @ Tankt <br /> 930 E.Victor Road 930 E. Victor Road Site No. <br /> Lodi,Ca. Lodi,Ca. <br /> MECHANICAL LEAK DETECTOR TEST <br /> Product: (Ba Mfg Model# Serial# <br /> Submerged Pump: Red Jacket P7551 10021297-2825 <br /> Leak Detector: Red Jacket 116-056 FXIv - 40598-3013 <br /> Leak Detector Opening Time Test <br /> 1 Tum on Pump and record the step-through time from 0 psi to full pressure. 2 sec <br /> Functional Element Operation Test <br /> 2 <br /> Pump Running Pressure 222 PS <br /> 3 Shut-off Pressure 20 PS <br /> Resiliency Test(Bleed back) <br /> 4 Drain and measure amount of product from shut-off pressure to 0 psi. 50 MI <br /> 10 PSI Calibration <br /> 5 Using the calibration valve,create the proper leak rate @ 10 psi. 192 MI <br /> Confirm test leak @(per minute) <br /> Simulated Leak Test <br /> 6 With the simulated leak in the line active,dispense product from the nozzle. 1.2 GP <br /> Confirm Row rate through the nozzle @ <br /> Bottom Line (There are two tests the leak detector must pass in order for it to be considered acceptable.) <br /> Pass Fai <br /> 7A Leak Detector-Opening Time Test X <br /> 713 Leak Simulated Test Pass Fai <br /> Flow rate through nozzle <br /> X <br /> LEAK DETECTOR MUST PASS BOTH TEST IN#7 Pass Fai <br /> X <br /> Technician: Test Date: <br /> Performed by: Sacramento Equipment Maintenance Company,Inc. <br /> 2533 Connie Drive Connie Drive <br /> Sacramento,CA 95815 <br /> 916-925-2716 916-925-2816 FAX <br />