Laserfiche WebLink
UNDERGROUND STORAGE TANK <br /> OVERFILL PREVENTION EQUIPMENT INSPECTION REPORT FORM (Pagel of 1) <br /> Type of Action ❑Installation Inspection ❑Repair Inspection ❑x 36 Month Inspection <br /> I. FACILITY INFORMATION <br /> CERS ID Date of Overfill Prevention Equipment Inspection <br /> 10181885 11/9/2018 <br /> Business Name(Same as Facility Name or DBA-Doing Business As) <br /> VALLEY PACIFIC LODI PLANT & CARDLOCK <br /> Business Site Address City ZIP Code <br /> 930 E VICTOR RD LODI 95240 <br /> II. UNDERGROUND STORAGE TANK SERVICE TECHNICIAN INFORMATION <br /> Name of UST Service Technician Performing the Inspection(Print as shown on the ICC Certification.) Phone# <br /> Garrett Warren (916) 991-1100 <br /> Contractor/Tank Tester License# ICC Certification# ICC Certification Expiration Date <br /> CSLB#803616 8185019 10/2/2019 <br /> Overfill Prevention Equipment Inspection Training and Certifications(List applicable certifications.) <br /> Veeder-Root 842126 exp. 1-23-2019 OPW EVR 101018 exp. 6-9-2019 - -% �� 4 " <br /> ' <br /> R ,,�► J.D <br /> III. OVERFILL PREVENTION EQUIPMENT INSPECTION INFORMATION L <br /> Inspection Method ❑x Manufacturer Guidelines(Specify): <br /> Used: Manufacture's IOMs <br /> ❑X Industry Code or Engineering Standard(Specify): Industry Standard (see attached) <br /> ❑Engineered Method(Specify): ENVIR&4qiNTAI HEALTH <br /> DEE- RTIM5ENT <br /> Attach the inspection procedures and all documentation required to determine the results. #of Attached Pages 8 <br /> TANK ID:(By tank number,stored product,etc.) T6: 87 T7: 87 <br /> What is the tank inside diameter?(Inches) 96" 96" <br /> Is the fill piping secondarily contained? ❑Yes 0 No ❑Yes LE No ❑Yes ❑No ❑Yes ❑No <br /> Is the vent piping secondarily contained? ❑Yes I]No ❑Yes (]No ❑Yes ❑No ❑Yes ❑ No <br /> Overfill Prevention Equipment Manufacturer(s) OPw61sO <br /> What is the overfill prevention equipment response ❑x Shuts Off Flow ❑Shuts Off Flow ❑Shuts Off Flow ❑Shuts Off Flow <br /> when activated? ❑x Restricts Flow ❑Restricts Flow ❑Restricts Flow ❑Restricts Flow <br /> (Check all that apply.) <br /> ❑A/V Alarm ❑AIV Alarm ❑A/V Alarm ❑A/V Alarm <br /> Are flow restrictors installed on vent piping? ❑Yes ❑No ❑Yes ❑No ❑Yes ❑No ❑Yes ❑No <br /> At what level in the tank is the overfill prevention set <br /> to activate?(Inches from bottom of tank.) 86" <br /> What is the percent capacity of the tank at which the <br /> overfill prevention equipment activates? 95% <br /> Is the overfill prevention in proper operating condition ❑x Yes ❑Yes ❑Yes ❑Yes <br /> to respond when the substance reaches the <br /> appropriate level? ❑No(Specify in V) ElNo(Specify in V.) ElNo(Specify in V.) ElNo(Specify in V.) <br /> IV. SUMMARY OF INSPECTION RESULTS <br /> Overfill Prevention Inspection Results ❑x Pass ❑Fai­lj ❑ Pass 0 Fail ❑ Pass ❑Fail ❑Pass ❑Fail <br /> V. COMMENTS <br /> Any items marked"Fail"must be explained in this section. Any additional comments may also be provided here. <br /> Was not able to remove the 87, 9,000 gallon tank drop tube. The bucket spun while trying to remove the top pipe in the <br /> spill bucket. Not able to remove the plug in the sumps to verify if the site has ball floats. <br /> VI. CERTIFICATION BY UST SERVICE TECHNICIAN CONDUCTING THIS INSPECTION <br /> I hereby certify that the overfill prevention equipment was inspected in accordance with California Code of Regulations,Title 23, <br /> Division 3,Chapter 16,Section 2637.2 and all the information contained herein is accurate. <br /> UST Service Technician Signature <br /> If the facility has more components than this o d tional copies of ►s page may 6e-attached. <br /> CERS=Cafifomia Environmental Reporting System,ID=Identification,UST=Underground Storage Tank,ICC=International Code Council,AA/=Audible and Visual <br />