Laserfiche WebLink
INVOICE #JB000342 AFFORDA-TE$T TEST DATE: 01/09/99 <br /> POB 36 - 26515 N SACRAMENTO BL <br /> THORNTON, CA 95686-0036 <br /> (209)794-0102 FAX ( 209)794-0112 <br /> TANK STATUS EVALUATION REPORT <br /> ----------------------------- <br /> ***** CUSTOMER DATA ***** <br /> ***** SITE DATA ***** <br /> STOCKTON SERVICE STATION EQUIP. 3 PALMS GROCERY <br /> P.O.BOX 508 6732 WATERLOO RD. <br /> 808 N. UNION ST. @ FAIRCHILD RD. <br /> STOCKTON, CA. STOCKTON, CA. <br /> 95201 <br /> CONTACT: JIM CONTACT: MENDONCA, RUDY <br /> PHONE #: (209)464-8333 PHONE #: ( 209)931-6048 <br /> ***** COMMENT LINES ***** <br /> TWO 1K TANKS - SUCTION SYSTEM - BALANCED VR - RONAN SENSOR UNIT <br /> CURRENT EPA STANDARDS DICTATE THAT FOR UNDERGROUND FUEL TANKS, THE <br /> THE MAXIMUM ALLOWABLE HOURLY LEAK/GAIN RATE IS .05 GALLONS. <br /> ULLAGE TESTS ARE ON A PASS/FAIL BASIS ONLY. <br /> TANK #1 : REG UNLEADED TYPE: STEEL RATE: . 031170 G.P.H. LOSS <br /> ULLAGE: PASS SIGNAL/NOISE: -. 13 <br /> TANK IS TIGHT. <br /> TANK #2: PLUS UNLEADED TYPE: STEEL RATE: . 011639 G.P.H. GAIN <br /> ULLAGE: PASS SIGNAL/NOISE: -. 11 <br /> TANK IS TIGHT. <br /> EQUIPMENT: USTEST <br /> OTTL# 97-1143 <br /> OPERATOR: LYLE D. NIMMO SIGNATURE: <br />