Laserfiche WebLink
INVOICE #WC000196 TEST DATE: 06/13/95 <br /> USTest 2000 / P <br /> CHAMPION PRECISION TANK TESTING <br /> P.O. BOX 13059 <br /> SACRAMENTO, CALIF, 95813-3059 <br /> TANK STATUS EVALUATION REPORT <br /> ----------------------------- <br /> ***** CUSTOMER DATA ***** ***** SITE DATA ***** <br /> OIL EQUIPTMENT SERVICE THREE PALMS MARKET <br /> P.O.BOX 950 6733 WATERLOO RD. <br /> HWY 88 EAST OF HWY 99 <br /> SAN ANDREAS,CA STOCKTON,CA. <br /> 95249 95215 <br /> CONTACT: KEITH TALLIS CONTACT: STORE MANAGER <br /> PHONE # : 209-754-1808 PHONE # : 916-931-6048 <br /> ***** COMMENT LINES ***** <br /> TANK AND PRODUCT LINES HAVE SECONDARY CONTAINMENT <br /> SUCTION SYSTEM,NEW PUMPS <br /> CURRENT EPA STANDARDS DICTATE <br /> THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE LEAK/GAIN RATE <br /> OVER THE PERIOD OF ONE HOUR IS .05 GALLONS. <br /> TANK #1: REG UNLEADED TYPE:FIBERGLASS RATE: .011012 G.P.H <br /> TANK IS TIGHT. <br /> TANK #2: PLUS UNLEADED TYPE:FIBERGLASS RATE: .016284 G.P.H <br /> TANK IS TIGHT. <br /> OPERATOR: SIGNATURE: \ {� DATE: <br /> Lt)l l l 11a' �[ + J�iF=y-- \IND— <br />