Page 2 of 3 <br /> Nolan to Le <br /> Stockton UST Inspection Response <br /> February 3, 2005 <br /> • Item #16 — SJCEHD noted that the written UST monitoring plan needed to <br /> be updated and submitted to the County by February 4, 2005. PG&E has <br /> updated the plan and a copy is attached to this report. <br /> • Item #18 — SJCEHD noted two Veeder-Root alarm records, dated March <br /> 31, 2004 and July 19, 2004. The County requested additional information <br /> regarding the responses to these alarms and input on how future alarm <br /> actions will be documented. The March 31 alarm was related to a leak on <br /> the delivery hose connection, causing fuel to enter the sump. The fuel <br /> was removed on April 5, 2004. The July 19 alarm was caused by a faulty <br /> line leak detector which was replaced on that same day. PG&E would like <br /> to note however, that the Stockton Division is instituting a new alarm <br /> tracking form to better document alarms and related responses. A copy of <br /> the form is included in Attachment 2 of the UST Monitoring Plan. This <br /> form may be modified in the future as needed. <br /> • Item #19 — SJCEHD noted that positive shutdown could not be confirmed <br /> during the January 4 testing due to the sump sensor problems. PG&Es <br /> contractor, Accutest, returned to the facility on January 24, 2005 and <br /> completed the testing, and confirmed positive shutdown. A copy of the <br /> monitoring system certification results was submitted by fax to the County <br /> on January 24, 2005. A copy is also attached to this report. <br /> • Item #20 — SJCEHD noted that the unleaded line leak detector could not <br /> be tested on January 4, 2005 due to the sensor problems. PG&Es <br /> contractor, Accutest, returned to the facility on January 24, 2005 and <br /> completed the testing, and confirmed proper operation of the line leak <br /> detector. A copy of the results was submitted by fax to the County on <br /> January 24, 2005, and a copy is also attached to this report. <br /> • In addition, a copy of the Secondary Containment Testing Report form for <br /> the test performed on January 4, 2005 is attached. <br /> It is a pleasure to provide this information. As always, PG&E is committed to <br /> environmental compliance and continued improvement. We also consider a <br /> positive relationship with our regulatory agencies to be a vital part of our <br /> program. If you have any questions, or need additional information, please feel <br /> free to call me at (209) 942-1566. <br /> Sincerely, <br /> PACIFIC GAS /AN <br /> � ELECTRIC COMPANY <br /> Erich Nolan, RG, CHMM <br /> Environmental Field Specialist <br /> Stockton Division <br />